⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 80 Ampere ved 30 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 80 A over 30 m ved 400V.

Copper Cable (≤3% Drop)25 mm²Drop: 3.56V (0.89%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 4.19V (1.05%)
Voltage at Load396.4 VLine Loss: 493.1 W
Max Power & Breaker55.43 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A59.31 V (14.83%)340.7 V97.83 V (24.46%)8217.6 WDrop High
2.5 mm²24 A18 A35.58 V (8.9%)364.4 V58.7 V (14.67%)4930.6 WDrop High
4 mm²32 A25 A22.24 V (5.56%)377.8 V36.68 V (9.17%)3081.6 WDrop High
6 mm²41 A32 A14.83 V (3.71%)385.2 V24.46 V (6.11%)2054.4 WDrop High
10 mm²57 A44 A8.9 V (2.22%)391.1 V14.67 V (3.67%)1232.6 WDrop High
16 mm²76 A59 A5.56 V (1.39%)394.4 V9.17 V (2.29%)770.4 WDrop High
25 mm²101 A78 A3.56 V (0.89%)396.4 V5.87 V (1.47%)493.1 W✓ OK (≤3%)
35 mm²125 A97 A2.54 V (0.64%)397.5 V4.19 V (1.05%)352.2 W✓ OK (≤3%)
50 mm²151 A118 A1.78 V (0.44%)398.2 V2.93 V (0.73%)246.5 W✓ OK (≤3%)
70 mm²192 A150 A1.27 V (0.32%)398.7 V2.1 V (0.52%)176.1 W✓ OK (≤3%)
95 mm²232 A181 A0.94 V (0.23%)399.1 V1.54 V (0.39%)129.8 W✓ OK (≤3%)
120 mm²269 A210 A0.74 V (0.19%)399.3 V1.22 V (0.31%)102.7 W✓ OK (≤3%)
150 mm²309 A241 A0.59 V (0.15%)399.4 V0.98 V (0.24%)82.2 W✓ OK (≤3%)
185 mm²353 A275 A0.48 V (0.12%)399.5 V0.79 V (0.2%)66.6 W✓ OK (≤3%)
240 mm²415 A324 A0.37 V (0.09%)399.6 V0.61 V (0.15%)51.4 W✓ OK (≤3%)
300 mm²477 A372 A0.3 V (0.07%)399.7 V0.49 V (0.12%)41.1 W✓ OK (≤3%)
400 mm²570 A445 A0.22 V (0.06%)399.8 V0.37 V (0.09%)30.8 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 80 Ampere ved 30 Meter (400V)

Hvilket kabeltværsnit kræves til 80A ved 30 meter (400V)?

Til 80 Ampere over 30 meter ved 400V anbefales 25 mm² kobberkabel (spændingsfald 3.56V / 0.89%).

Hvor mange kW svarer 80A ved 400V til?

Det svarer til 55.43 kW med en anbefalet sikring på 80A.