Kabeltværsnit for 800 Ampere ved 500 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 800 A over 500 m ved 400V.

Copper Cable (≤3% Drop)4× 400 mm²Drop: 9.27V (2.32%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 61.14V (15.29%)
Voltage at Load390.7 VLine Loss: 12840.0 W
Max Power & Breaker554.26 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A9884.24 V (2471.06%)0.0 V16304.37 V (4076.09%)13696000.0 WDrop High
2.5 mm²24 A18 A5930.54 V (1482.64%)0.0 V9782.62 V (2445.66%)8217600.0 WDrop High
4 mm²32 A25 A3706.59 V (926.65%)0.0 V6114.14 V (1528.53%)5136000.0 WDrop High
6 mm²41 A32 A2471.06 V (617.76%)0.0 V4076.09 V (1019.02%)3424000.0 WDrop High
10 mm²57 A44 A1482.64 V (370.66%)0.0 V2445.66 V (611.41%)2054400.0 WDrop High
16 mm²76 A59 A926.65 V (231.66%)0.0 V1528.53 V (382.13%)1284000.0 WDrop High
25 mm²101 A78 A593.05 V (148.26%)0.0 V978.26 V (244.57%)821760.0 WDrop High
35 mm²125 A97 A423.61 V (105.9%)0.0 V698.76 V (174.69%)586971.4 WDrop High
50 mm²151 A118 A296.53 V (74.13%)103.5 V489.13 V (122.28%)410880.0 WDrop High
70 mm²192 A150 A211.81 V (52.95%)188.2 V349.38 V (87.34%)293485.7 WDrop High
95 mm²232 A181 A156.07 V (39.02%)243.9 V257.44 V (64.36%)216252.6 WDrop High
120 mm²269 A210 A123.55 V (30.89%)276.4 V203.8 V (50.95%)171200.0 WDrop High
150 mm²309 A241 A98.84 V (24.71%)301.2 V163.04 V (40.76%)136960.0 WDrop High
185 mm²353 A275 A80.14 V (20.04%)319.9 V132.2 V (33.05%)111048.6 WDrop High
240 mm²415 A324 A61.78 V (15.44%)338.2 V101.9 V (25.48%)85600.0 WDrop High
300 mm²477 A372 A49.42 V (12.36%)350.6 V81.52 V (20.38%)68480.0 WDrop High
400 mm²570 A445 A37.07 V (9.27%)362.9 V61.14 V (15.29%)51360.0 WDrop High

FAQ — Kabeltværsnit for 800 Ampere ved 500 Meter (400V)

Hvilket kabeltværsnit kræves til 800A ved 500 meter (400V)?

Til 800 Ampere over 500 meter ved 400V anbefales 4× 400 mm² kobberkabel (spændingsfald 9.27V / 2.32%).

Hvor mange kW svarer 800A ved 400V til?

Det svarer til 554.26 kW med en anbefalet sikring på 800A.