Kabelquerschnitt für 100 Ampere bei 35 Meter (230V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 100 A über 35 m einfache Leitungslänge bei 230V.

Copper Cable (≤3% Drop)25 mm²Drop: 5.99V (2.61%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 4.94V (2.15%)
Voltage at Load224.0 VLine Loss: 599.2 W
Max Power & Breaker23.0 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A99.87 V (43.42%)130.1 V164.73 V (71.62%)9986.7 WDrop High
2.5 mm²24 A18 A59.92 V (26.05%)170.1 V98.84 V (42.97%)5992.0 WDrop High
4 mm²32 A25 A37.45 V (16.28%)192.6 V61.78 V (26.86%)3745.0 WDrop High
6 mm²41 A32 A24.97 V (10.86%)205.0 V41.18 V (17.91%)2496.7 WDrop High
10 mm²57 A44 A14.98 V (6.51%)215.0 V24.71 V (10.74%)1498.0 WDrop High
16 mm²76 A59 A9.36 V (4.07%)220.6 V15.44 V (6.71%)936.2 WDrop High
25 mm²101 A78 A5.99 V (2.61%)224.0 V9.88 V (4.3%)599.2 W✓ OK (≤3%)
35 mm²125 A97 A4.28 V (1.86%)225.7 V7.06 V (3.07%)428.0 W✓ OK (≤3%)
50 mm²151 A118 A3.0 V (1.3%)227.0 V4.94 V (2.15%)299.6 W✓ OK (≤3%)
70 mm²192 A150 A2.14 V (0.93%)227.9 V3.53 V (1.53%)214.0 W✓ OK (≤3%)
95 mm²232 A181 A1.58 V (0.69%)228.4 V2.6 V (1.13%)157.7 W✓ OK (≤3%)
120 mm²269 A210 A1.25 V (0.54%)228.8 V2.06 V (0.9%)124.8 W✓ OK (≤3%)
150 mm²309 A241 A1.0 V (0.43%)229.0 V1.65 V (0.72%)99.9 W✓ OK (≤3%)
185 mm²353 A275 A0.81 V (0.35%)229.2 V1.34 V (0.58%)81.0 W✓ OK (≤3%)
240 mm²415 A324 A0.62 V (0.27%)229.4 V1.03 V (0.45%)62.4 W✓ OK (≤3%)
300 mm²477 A372 A0.5 V (0.22%)229.5 V0.82 V (0.36%)49.9 W✓ OK (≤3%)
400 mm²570 A445 A0.37 V (0.16%)229.6 V0.62 V (0.27%)37.5 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 100 Ampere bei 35 Meter (230V)

Welcher Kabelquerschnitt wird für 100A bei 35m (230V) benötigt?

Für 100 Ampere über 35 Meter bei 230V wird ein Kupferkabel von 25 mm² empfohlen, um den Spannungsfall unter 3% (5.99V bzw. 2.61%) zu halten.

Wie hoch ist die maximale Leistung bei 100A und 230V?

Die übertragbare Leistung beträgt 23.0 kW bei einer empfohlenen Absicherung von 100A.