⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 160 Ampere bei 45 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 160 A über 45 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)70 mm²Drop: 3.81V (0.95%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 4.63V (1.16%)
Voltage at Load396.2 VLine Loss: 1056.5 W
Max Power & Breaker110.85 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A177.92 V (44.48%)222.1 V293.48 V (73.37%)49305.6 WDrop High
2.5 mm²24 A18 A106.75 V (26.69%)293.3 V176.09 V (44.02%)29583.4 WDrop High
4 mm²32 A25 A66.72 V (16.68%)333.3 V110.05 V (27.51%)18489.6 WDrop High
6 mm²41 A32 A44.48 V (11.12%)355.5 V73.37 V (18.34%)12326.4 WDrop High
10 mm²57 A44 A26.69 V (6.67%)373.3 V44.02 V (11.01%)7395.8 WDrop High
16 mm²76 A59 A16.68 V (4.17%)383.3 V27.51 V (6.88%)4622.4 WDrop High
25 mm²101 A78 A10.67 V (2.67%)389.3 V17.61 V (4.4%)2958.3 WDrop High
35 mm²125 A97 A7.62 V (1.91%)392.4 V12.58 V (3.14%)2113.1 WDrop High
50 mm²151 A118 A5.34 V (1.33%)394.7 V8.8 V (2.2%)1479.2 WDrop High
70 mm²192 A150 A3.81 V (0.95%)396.2 V6.29 V (1.57%)1056.5 W✓ OK (≤3%)
95 mm²232 A181 A2.81 V (0.7%)397.2 V4.63 V (1.16%)778.5 W✓ OK (≤3%)
120 mm²269 A210 A2.22 V (0.56%)397.8 V3.67 V (0.92%)616.3 W✓ OK (≤3%)
150 mm²309 A241 A1.78 V (0.44%)398.2 V2.93 V (0.73%)493.1 W✓ OK (≤3%)
185 mm²353 A275 A1.44 V (0.36%)398.6 V2.38 V (0.59%)399.8 W✓ OK (≤3%)
240 mm²415 A324 A1.11 V (0.28%)398.9 V1.83 V (0.46%)308.2 W✓ OK (≤3%)
300 mm²477 A372 A0.89 V (0.22%)399.1 V1.47 V (0.37%)246.5 W✓ OK (≤3%)
400 mm²570 A445 A0.67 V (0.17%)399.3 V1.1 V (0.28%)184.9 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 160 Ampere bei 45 Meter (400V)

Welcher Kabelquerschnitt wird für 160A bei 45m (400V) benötigt?

Für 160 Ampere über 45 Meter bei 400V wird ein Kupferkabel von 70 mm² empfohlen, um den Spannungsfall unter 3% (3.81V bzw. 0.95%) zu halten.

Wie hoch ist die maximale Leistung bei 160A und 400V?

Die übertragbare Leistung beträgt 110.85 kW bei einer empfohlenen Absicherung von 160A.