Kabelquerschnitt für 225 Ampere bei 175 Meter (230V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 225 A über 175 m einfache Leitungslänge bei 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 5.62V (2.44%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.95V (3.02%)
Voltage at Load224.4 VLine Loss: 1263.9 W
Max Power & Breaker51.75 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1123.5 V (488.48%)0.0 V1853.25 V (805.76%)252787.5 WDrop High
2.5 mm²24 A18 A674.1 V (293.09%)0.0 V1111.95 V (483.46%)151672.5 WDrop High
4 mm²32 A25 A421.31 V (183.18%)0.0 V694.97 V (302.16%)94795.3 WDrop High
6 mm²41 A32 A280.88 V (122.12%)0.0 V463.31 V (201.44%)63196.9 WDrop High
10 mm²57 A44 A168.52 V (73.27%)61.5 V277.99 V (120.86%)37918.1 WDrop High
16 mm²76 A59 A105.33 V (45.79%)124.7 V173.74 V (75.54%)23698.8 WDrop High
25 mm²101 A78 A67.41 V (29.31%)162.6 V111.19 V (48.35%)15167.2 WDrop High
35 mm²125 A97 A48.15 V (20.93%)181.9 V79.42 V (34.53%)10833.7 WDrop High
50 mm²151 A118 A33.7 V (14.65%)196.3 V55.6 V (24.17%)7583.6 WDrop High
70 mm²192 A150 A24.07 V (10.47%)205.9 V39.71 V (17.27%)5416.9 WDrop High
95 mm²232 A181 A17.74 V (7.71%)212.3 V29.26 V (12.72%)3991.4 WDrop High
120 mm²269 A210 A14.04 V (6.11%)216.0 V23.17 V (10.07%)3159.8 WDrop High
150 mm²309 A241 A11.23 V (4.88%)218.8 V18.53 V (8.06%)2527.9 W~ ≤5%
185 mm²353 A275 A9.11 V (3.96%)220.9 V15.03 V (6.53%)2049.6 W~ ≤5%
240 mm²415 A324 A7.02 V (3.05%)223.0 V11.58 V (5.04%)1579.9 W~ ≤5%
300 mm²477 A372 A5.62 V (2.44%)224.4 V9.27 V (4.03%)1263.9 W✓ OK (≤3%)
400 mm²570 A445 A4.21 V (1.83%)225.8 V6.95 V (3.02%)948.0 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 225 Ampere bei 175 Meter (230V)

Welcher Kabelquerschnitt wird für 225A bei 175m (230V) benötigt?

Für 225 Ampere über 175 Meter bei 230V wird ein Kupferkabel von 300 mm² empfohlen, um den Spannungsfall unter 3% (5.62V bzw. 2.44%) zu halten.

Wie hoch ist die maximale Leistung bei 225A und 230V?

Die übertragbare Leistung beträgt 51.75 kW bei einer empfohlenen Absicherung von 225A.