Kabelquerschnitt für 275 Ampere bei 90 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 275 A über 90 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)150 mm²Drop: 6.12V (1.53%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 8.18V (2.04%)
Voltage at Load393.9 VLine Loss: 2913.1 W
Max Power & Breaker190.53 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 275A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A611.59 V (152.9%)0.0 V1008.83 V (252.21%)291307.5 WDrop High
2.5 mm²24 A18 A366.95 V (91.74%)33.0 V605.3 V (151.32%)174784.5 WDrop High
4 mm²32 A25 A229.35 V (57.34%)170.7 V378.31 V (94.58%)109240.3 WDrop High
6 mm²41 A32 A152.9 V (38.22%)247.1 V252.21 V (63.05%)72826.9 WDrop High
10 mm²57 A44 A91.74 V (22.93%)308.3 V151.32 V (37.83%)43696.1 WDrop High
16 mm²76 A59 A57.34 V (14.33%)342.7 V94.58 V (23.64%)27310.1 WDrop High
25 mm²101 A78 A36.7 V (9.17%)363.3 V60.53 V (15.13%)17478.5 WDrop High
35 mm²125 A97 A26.21 V (6.55%)373.8 V43.24 V (10.81%)12484.6 WDrop High
50 mm²151 A118 A18.35 V (4.59%)381.7 V30.26 V (7.57%)8739.2 WDrop High
70 mm²192 A150 A13.11 V (3.28%)386.9 V21.62 V (5.4%)6242.3 WDrop High
95 mm²232 A181 A9.66 V (2.41%)390.3 V15.93 V (3.98%)4599.6 WDrop High
120 mm²269 A210 A7.64 V (1.91%)392.4 V12.61 V (3.15%)3641.3 WDrop High
150 mm²309 A241 A6.12 V (1.53%)393.9 V10.09 V (2.52%)2913.1 W✓ OK (≤3%)
185 mm²353 A275 A4.96 V (1.24%)395.0 V8.18 V (2.04%)2362.0 W✓ OK (≤3%)
240 mm²415 A324 A3.82 V (0.96%)396.2 V6.31 V (1.58%)1820.7 W✓ OK (≤3%)
300 mm²477 A372 A3.06 V (0.76%)396.9 V5.04 V (1.26%)1456.5 W✓ OK (≤3%)
400 mm²570 A445 A2.29 V (0.57%)397.7 V3.78 V (0.95%)1092.4 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 275 Ampere bei 90 Meter (400V)

Welcher Kabelquerschnitt wird für 275A bei 90m (400V) benötigt?

Für 275 Ampere über 90 Meter bei 400V wird ein Kupferkabel von 150 mm² empfohlen, um den Spannungsfall unter 3% (6.12V bzw. 1.53%) zu halten.

Wie hoch ist die maximale Leistung bei 275A und 400V?

Die übertragbare Leistung beträgt 190.53 kW bei einer empfohlenen Absicherung von 300A.