Kabelquerschnitt für 30 Ampere bei 80 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 30 A über 80 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)10 mm²Drop: 8.9V (2.22%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 9.17V (2.29%)
Voltage at Load391.1 VLine Loss: 462.2 W
Max Power & Breaker20.78 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A59.31 V (14.83%)340.7 V97.83 V (24.46%)3081.6 WDrop High
2.5 mm²24 A18 A35.58 V (8.9%)364.4 V58.7 V (14.67%)1849.0 WDrop High
4 mm²32 A25 A22.24 V (5.56%)377.8 V36.68 V (9.17%)1155.6 WDrop High
6 mm²41 A32 A14.83 V (3.71%)385.2 V24.46 V (6.11%)770.4 W~ ≤5%
10 mm²57 A44 A8.9 V (2.22%)391.1 V14.67 V (3.67%)462.2 W✓ OK (≤3%)
16 mm²76 A59 A5.56 V (1.39%)394.4 V9.17 V (2.29%)288.9 W✓ OK (≤3%)
25 mm²101 A78 A3.56 V (0.89%)396.4 V5.87 V (1.47%)184.9 W✓ OK (≤3%)
35 mm²125 A97 A2.54 V (0.64%)397.5 V4.19 V (1.05%)132.1 W✓ OK (≤3%)
50 mm²151 A118 A1.78 V (0.44%)398.2 V2.93 V (0.73%)92.4 W✓ OK (≤3%)
70 mm²192 A150 A1.27 V (0.32%)398.7 V2.1 V (0.52%)66.0 W✓ OK (≤3%)
95 mm²232 A181 A0.94 V (0.23%)399.1 V1.54 V (0.39%)48.7 W✓ OK (≤3%)
120 mm²269 A210 A0.74 V (0.19%)399.3 V1.22 V (0.31%)38.5 W✓ OK (≤3%)
150 mm²309 A241 A0.59 V (0.15%)399.4 V0.98 V (0.24%)30.8 W✓ OK (≤3%)
185 mm²353 A275 A0.48 V (0.12%)399.5 V0.79 V (0.2%)25.0 W✓ OK (≤3%)
240 mm²415 A324 A0.37 V (0.09%)399.6 V0.61 V (0.15%)19.3 W✓ OK (≤3%)
300 mm²477 A372 A0.3 V (0.07%)399.7 V0.49 V (0.12%)15.4 W✓ OK (≤3%)
400 mm²570 A445 A0.22 V (0.06%)399.8 V0.37 V (0.09%)11.6 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 30 Ampere bei 80 Meter (400V)

Welcher Kabelquerschnitt wird für 30A bei 80m (400V) benötigt?

Für 30 Ampere über 80 Meter bei 400V wird ein Kupferkabel von 10 mm² empfohlen, um den Spannungsfall unter 3% (8.9V bzw. 2.22%) zu halten.

Wie hoch ist die maximale Leistung bei 30A und 400V?

Die übertragbare Leistung beträgt 20.78 kW bei einer empfohlenen Absicherung von 30A.