Kabelquerschnitt für 32 Ampere bei 5 Meter (230V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 32 A über 5 m einfache Leitungslänge bei 230V.

Copper Cable (≤3% Drop)4 mm²Drop: 1.71V (0.74%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 1.88V (0.82%)
Voltage at Load228.3 VLine Loss: 54.8 W
Max Power & Breaker7.36 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4.57 V (1.98%)225.4 V7.53 V (3.27%)146.1 WDrop High
2.5 mm²24 A18 A2.74 V (1.19%)227.3 V4.52 V (1.96%)87.7 WDrop High
4 mm²32 A25 A1.71 V (0.74%)228.3 V2.82 V (1.23%)54.8 W✓ OK (≤3%)
6 mm²41 A32 A1.14 V (0.5%)228.9 V1.88 V (0.82%)36.5 W✓ OK (≤3%)
10 mm²57 A44 A0.68 V (0.3%)229.3 V1.13 V (0.49%)21.9 W✓ OK (≤3%)
16 mm²76 A59 A0.43 V (0.19%)229.6 V0.71 V (0.31%)13.7 W✓ OK (≤3%)
25 mm²101 A78 A0.27 V (0.12%)229.7 V0.45 V (0.2%)8.8 W✓ OK (≤3%)
35 mm²125 A97 A0.2 V (0.09%)229.8 V0.32 V (0.14%)6.3 W✓ OK (≤3%)
50 mm²151 A118 A0.14 V (0.06%)229.9 V0.23 V (0.1%)4.4 W✓ OK (≤3%)
70 mm²192 A150 A0.1 V (0.04%)229.9 V0.16 V (0.07%)3.1 W✓ OK (≤3%)
95 mm²232 A181 A0.07 V (0.03%)229.9 V0.12 V (0.05%)2.3 W✓ OK (≤3%)
120 mm²269 A210 A0.06 V (0.02%)229.9 V0.09 V (0.04%)1.8 W✓ OK (≤3%)
150 mm²309 A241 A0.05 V (0.02%)230.0 V0.08 V (0.03%)1.5 W✓ OK (≤3%)
185 mm²353 A275 A0.04 V (0.02%)230.0 V0.06 V (0.03%)1.2 W✓ OK (≤3%)
240 mm²415 A324 A0.03 V (0.01%)230.0 V0.05 V (0.02%)0.9 W✓ OK (≤3%)
300 mm²477 A372 A0.02 V (0.01%)230.0 V0.04 V (0.02%)0.7 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.01%)230.0 V0.03 V (0.01%)0.5 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 32 Ampere bei 5 Meter (230V)

Welcher Kabelquerschnitt wird für 32A bei 5m (230V) benötigt?

Für 32 Ampere über 5 Meter bei 230V wird ein Kupferkabel von 4 mm² empfohlen, um den Spannungsfall unter 3% (1.71V bzw. 0.74%) zu halten.

Wie hoch ist die maximale Leistung bei 32A und 230V?

Die übertragbare Leistung beträgt 7.36 kW bei einer empfohlenen Absicherung von 32A.