Kabelquerschnitt für 325 Ampere bei 40 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 325 A über 40 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)185 mm²Drop: 2.6V (0.65%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 2.65V (0.66%)
Voltage at Load397.4 VLine Loss: 1466.2 W
Max Power & Breaker225.17 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A321.24 V (80.31%)78.8 V529.89 V (132.47%)180830.0 WDrop High
2.5 mm²24 A18 A192.74 V (48.19%)207.3 V317.94 V (79.48%)108498.0 WDrop High
4 mm²32 A25 A120.46 V (30.12%)279.5 V198.71 V (49.68%)67811.2 WDrop High
6 mm²41 A32 A80.31 V (20.08%)319.7 V132.47 V (33.12%)45207.5 WDrop High
10 mm²57 A44 A48.19 V (12.05%)351.8 V79.48 V (19.87%)27124.5 WDrop High
16 mm²76 A59 A30.12 V (7.53%)369.9 V49.68 V (12.42%)16952.8 WDrop High
25 mm²101 A78 A19.27 V (4.82%)380.7 V31.79 V (7.95%)10849.8 WDrop High
35 mm²125 A97 A13.77 V (3.44%)386.2 V22.71 V (5.68%)7749.9 WDrop High
50 mm²151 A118 A9.64 V (2.41%)390.4 V15.9 V (3.97%)5424.9 WDrop High
70 mm²192 A150 A6.88 V (1.72%)393.1 V11.35 V (2.84%)3874.9 WDrop High
95 mm²232 A181 A5.07 V (1.27%)394.9 V8.37 V (2.09%)2855.2 WDrop High
120 mm²269 A210 A4.02 V (1.0%)396.0 V6.62 V (1.66%)2260.4 WDrop High
150 mm²309 A241 A3.21 V (0.8%)396.8 V5.3 V (1.32%)1808.3 WDrop High
185 mm²353 A275 A2.6 V (0.65%)397.4 V4.3 V (1.07%)1466.2 W✓ OK (≤3%)
240 mm²415 A324 A2.01 V (0.5%)398.0 V3.31 V (0.83%)1130.2 W✓ OK (≤3%)
300 mm²477 A372 A1.61 V (0.4%)398.4 V2.65 V (0.66%)904.1 W✓ OK (≤3%)
400 mm²570 A445 A1.2 V (0.3%)398.8 V1.99 V (0.5%)678.1 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 325 Ampere bei 40 Meter (400V)

Welcher Kabelquerschnitt wird für 325A bei 40m (400V) benötigt?

Für 325 Ampere über 40 Meter bei 400V wird ein Kupferkabel von 185 mm² empfohlen, um den Spannungsfall unter 3% (2.6V bzw. 0.65%) zu halten.

Wie hoch ist die maximale Leistung bei 325A und 400V?

Die übertragbare Leistung beträgt 225.17 kW bei einer empfohlenen Absicherung von 350A.