⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 40 Ampere bei 70 Meter (230V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 40 A über 70 m einfache Leitungslänge bei 230V.

Copper Cable (≤3% Drop)25 mm²Drop: 4.79V (2.08%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 5.65V (2.46%)
Voltage at Load225.2 VLine Loss: 191.7 W
Max Power & Breaker9.2 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A79.89 V (34.74%)150.1 V131.79 V (57.3%)3195.7 WDrop High
2.5 mm²24 A18 A47.94 V (20.84%)182.1 V79.07 V (34.38%)1917.4 WDrop High
4 mm²32 A25 A29.96 V (13.03%)200.0 V49.42 V (21.49%)1198.4 WDrop High
6 mm²41 A32 A19.97 V (8.68%)210.0 V32.95 V (14.32%)798.9 WDrop High
10 mm²57 A44 A11.98 V (5.21%)218.0 V19.77 V (8.59%)479.4 WDrop High
16 mm²76 A59 A7.49 V (3.26%)222.5 V12.36 V (5.37%)299.6 W~ ≤5%
25 mm²101 A78 A4.79 V (2.08%)225.2 V7.91 V (3.44%)191.7 W✓ OK (≤3%)
35 mm²125 A97 A3.42 V (1.49%)226.6 V5.65 V (2.46%)137.0 W✓ OK (≤3%)
50 mm²151 A118 A2.4 V (1.04%)227.6 V3.95 V (1.72%)95.9 W✓ OK (≤3%)
70 mm²192 A150 A1.71 V (0.74%)228.3 V2.82 V (1.23%)68.5 W✓ OK (≤3%)
95 mm²232 A181 A1.26 V (0.55%)228.7 V2.08 V (0.9%)50.5 W✓ OK (≤3%)
120 mm²269 A210 A1.0 V (0.43%)229.0 V1.65 V (0.72%)39.9 W✓ OK (≤3%)
150 mm²309 A241 A0.8 V (0.35%)229.2 V1.32 V (0.57%)32.0 W✓ OK (≤3%)
185 mm²353 A275 A0.65 V (0.28%)229.4 V1.07 V (0.46%)25.9 W✓ OK (≤3%)
240 mm²415 A324 A0.5 V (0.22%)229.5 V0.82 V (0.36%)20.0 W✓ OK (≤3%)
300 mm²477 A372 A0.4 V (0.17%)229.6 V0.66 V (0.29%)16.0 W✓ OK (≤3%)
400 mm²570 A445 A0.3 V (0.13%)229.7 V0.49 V (0.21%)12.0 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 40 Ampere bei 70 Meter (230V)

Welcher Kabelquerschnitt wird für 40A bei 70m (230V) benötigt?

Für 40 Ampere über 70 Meter bei 230V wird ein Kupferkabel von 25 mm² empfohlen, um den Spannungsfall unter 3% (4.79V bzw. 2.08%) zu halten.

Wie hoch ist die maximale Leistung bei 40A und 230V?

Die übertragbare Leistung beträgt 9.2 kW bei einer empfohlenen Absicherung von 40A.