⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 400 Ampere bei 80 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 400 A über 80 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)240 mm²Drop: 4.94V (1.24%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.89V (1.22%)
Voltage at Load395.1 VLine Loss: 3424.0 W
Max Power & Breaker277.13 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A790.74 V (197.68%)0.0 V1304.35 V (326.09%)547840.0 WDrop High
2.5 mm²24 A18 A474.44 V (118.61%)0.0 V782.61 V (195.65%)328704.0 WDrop High
4 mm²32 A25 A296.53 V (74.13%)103.5 V489.13 V (122.28%)205440.0 WDrop High
6 mm²41 A32 A197.68 V (49.42%)202.3 V326.09 V (81.52%)136960.0 WDrop High
10 mm²57 A44 A118.61 V (29.65%)281.4 V195.65 V (48.91%)82176.0 WDrop High
16 mm²76 A59 A74.13 V (18.53%)325.9 V122.28 V (30.57%)51360.0 WDrop High
25 mm²101 A78 A47.44 V (11.86%)352.6 V78.26 V (19.57%)32870.4 WDrop High
35 mm²125 A97 A33.89 V (8.47%)366.1 V55.9 V (13.98%)23478.9 WDrop High
50 mm²151 A118 A23.72 V (5.93%)376.3 V39.13 V (9.78%)16435.2 WDrop High
70 mm²192 A150 A16.94 V (4.24%)383.1 V27.95 V (6.99%)11739.4 WDrop High
95 mm²232 A181 A12.49 V (3.12%)387.5 V20.59 V (5.15%)8650.1 WDrop High
120 mm²269 A210 A9.88 V (2.47%)390.1 V16.3 V (4.08%)6848.0 WDrop High
150 mm²309 A241 A7.91 V (1.98%)392.1 V13.04 V (3.26%)5478.4 WDrop High
185 mm²353 A275 A6.41 V (1.6%)393.6 V10.58 V (2.64%)4441.9 WDrop High
240 mm²415 A324 A4.94 V (1.24%)395.1 V8.15 V (2.04%)3424.0 W✓ OK (≤3%)
300 mm²477 A372 A3.95 V (0.99%)396.0 V6.52 V (1.63%)2739.2 W✓ OK (≤3%)
400 mm²570 A445 A2.97 V (0.74%)397.0 V4.89 V (1.22%)2054.4 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 400 Ampere bei 80 Meter (400V)

Welcher Kabelquerschnitt wird für 400A bei 80m (400V) benötigt?

Für 400 Ampere über 80 Meter bei 400V wird ein Kupferkabel von 240 mm² empfohlen, um den Spannungsfall unter 3% (4.94V bzw. 1.24%) zu halten.

Wie hoch ist die maximale Leistung bei 400A und 400V?

Die übertragbare Leistung beträgt 277.13 kW bei einer empfohlenen Absicherung von 400A.