Kabelquerschnitt für 425 Ampere bei 400 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 425 A über 400 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 7.88V (1.97%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 25.99V (6.5%)
Voltage at Load392.1 VLine Loss: 5798.1 W
Max Power & Breaker294.45 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4200.8 V (1050.2%)0.0 V6929.36 V (1732.34%)3092300.0 WDrop High
2.5 mm²24 A18 A2520.48 V (630.12%)0.0 V4157.61 V (1039.4%)1855380.0 WDrop High
4 mm²32 A25 A1575.3 V (393.83%)0.0 V2598.51 V (649.63%)1159612.5 WDrop High
6 mm²41 A32 A1050.2 V (262.55%)0.0 V1732.34 V (433.08%)773075.0 WDrop High
10 mm²57 A44 A630.12 V (157.53%)0.0 V1039.4 V (259.85%)463845.0 WDrop High
16 mm²76 A59 A393.83 V (98.46%)6.2 V649.63 V (162.41%)289903.1 WDrop High
25 mm²101 A78 A252.05 V (63.01%)148.0 V415.76 V (103.94%)185538.0 WDrop High
35 mm²125 A97 A180.03 V (45.01%)220.0 V296.97 V (74.24%)132527.1 WDrop High
50 mm²151 A118 A126.02 V (31.51%)274.0 V207.88 V (51.97%)92769.0 WDrop High
70 mm²192 A150 A90.02 V (22.5%)310.0 V148.49 V (37.12%)66263.6 WDrop High
95 mm²232 A181 A66.33 V (16.58%)333.7 V109.41 V (27.35%)48825.8 WDrop High
120 mm²269 A210 A52.51 V (13.13%)347.5 V86.62 V (21.65%)38653.7 WDrop High
150 mm²309 A241 A42.01 V (10.5%)358.0 V69.29 V (17.32%)30923.0 WDrop High
185 mm²353 A275 A34.06 V (8.52%)365.9 V56.18 V (14.05%)25072.7 WDrop High
240 mm²415 A324 A26.26 V (6.56%)373.7 V43.31 V (10.83%)19326.9 WDrop High
300 mm²477 A372 A21.0 V (5.25%)379.0 V34.65 V (8.66%)15461.5 WDrop High
400 mm²570 A445 A15.75 V (3.94%)384.2 V25.99 V (6.5%)11596.1 W~ ≤5%

FAQ — Kabelquerschnitt für 425 Ampere bei 400 Meter (400V)

Welcher Kabelquerschnitt wird für 425A bei 400m (400V) benötigt?

Für 425 Ampere über 400 Meter bei 400V wird ein Kupferkabel von 2× 400 mm² empfohlen, um den Spannungsfall unter 3% (7.88V bzw. 1.97%) zu halten.

Wie hoch ist die maximale Leistung bei 425A und 400V?

Die übertragbare Leistung beträgt 294.45 kW bei einer empfohlenen Absicherung von 450A.