Kabelquerschnitt für 475 Ampere bei 120 Meter (230V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 475 A über 120 m einfache Leitungslänge bei 230V.

Copper Cable (≤3% Drop)400 mm²Drop: 6.1V (2.65%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 10.06V (4.37%)
Voltage at Load223.9 VLine Loss: 2897.0 W
Max Power & Breaker109.25 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1626.4 V (707.13%)0.0 V2682.8 V (1166.43%)772540.0 WDrop High
2.5 mm²24 A18 A975.84 V (424.28%)0.0 V1609.68 V (699.86%)463524.0 WDrop High
4 mm²32 A25 A609.9 V (265.17%)0.0 V1006.05 V (437.41%)289702.5 WDrop High
6 mm²41 A32 A406.6 V (176.78%)0.0 V670.7 V (291.61%)193135.0 WDrop High
10 mm²57 A44 A243.96 V (106.07%)0.0 V402.42 V (174.97%)115881.0 WDrop High
16 mm²76 A59 A152.47 V (66.29%)77.5 V251.51 V (109.35%)72425.6 WDrop High
25 mm²101 A78 A97.58 V (42.43%)132.4 V160.97 V (69.99%)46352.4 WDrop High
35 mm²125 A97 A69.7 V (30.31%)160.3 V114.98 V (49.99%)33108.9 WDrop High
50 mm²151 A118 A48.79 V (21.21%)181.2 V80.48 V (34.99%)23176.2 WDrop High
70 mm²192 A150 A34.85 V (15.15%)195.1 V57.49 V (25.0%)16554.4 WDrop High
95 mm²232 A181 A25.68 V (11.17%)204.3 V42.36 V (18.42%)12198.0 WDrop High
120 mm²269 A210 A20.33 V (8.84%)209.7 V33.53 V (14.58%)9656.8 WDrop High
150 mm²309 A241 A16.26 V (7.07%)213.7 V26.83 V (11.66%)7725.4 WDrop High
185 mm²353 A275 A13.19 V (5.73%)216.8 V21.75 V (9.46%)6263.8 WDrop High
240 mm²415 A324 A10.16 V (4.42%)219.8 V16.77 V (7.29%)4828.4 WDrop High
300 mm²477 A372 A8.13 V (3.54%)221.9 V13.41 V (5.83%)3862.7 W~ ≤5%
400 mm²570 A445 A6.1 V (2.65%)223.9 V10.06 V (4.37%)2897.0 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 475 Ampere bei 120 Meter (230V)

Welcher Kabelquerschnitt wird für 475A bei 120m (230V) benötigt?

Für 475 Ampere über 120 Meter bei 230V wird ein Kupferkabel von 400 mm² empfohlen, um den Spannungsfall unter 3% (6.1V bzw. 2.65%) zu halten.

Wie hoch ist die maximale Leistung bei 475A und 230V?

Die übertragbare Leistung beträgt 109.25 kW bei einer empfohlenen Absicherung von 500A.