Kabelquerschnitt für 475 Ampere bei 40 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 475 A über 40 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 2.35V (0.59%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.9V (0.73%)
Voltage at Load397.7 VLine Loss: 1931.3 W
Max Power & Breaker329.09 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A469.5 V (117.38%)0.0 V774.46 V (193.61%)386270.0 WDrop High
2.5 mm²24 A18 A281.7 V (70.43%)118.3 V464.67 V (116.17%)231762.0 WDrop High
4 mm²32 A25 A176.06 V (44.02%)223.9 V290.42 V (72.61%)144851.2 WDrop High
6 mm²41 A32 A117.38 V (29.34%)282.6 V193.61 V (48.4%)96567.5 WDrop High
10 mm²57 A44 A70.43 V (17.61%)329.6 V116.17 V (29.04%)57940.5 WDrop High
16 mm²76 A59 A44.02 V (11.0%)356.0 V72.61 V (18.15%)36212.8 WDrop High
25 mm²101 A78 A28.17 V (7.04%)371.8 V46.47 V (11.62%)23176.2 WDrop High
35 mm²125 A97 A20.12 V (5.03%)379.9 V33.19 V (8.3%)16554.4 WDrop High
50 mm²151 A118 A14.09 V (3.52%)385.9 V23.23 V (5.81%)11588.1 WDrop High
70 mm²192 A150 A10.06 V (2.52%)389.9 V16.6 V (4.15%)8277.2 WDrop High
95 mm²232 A181 A7.41 V (1.85%)392.6 V12.23 V (3.06%)6099.0 WDrop High
120 mm²269 A210 A5.87 V (1.47%)394.1 V9.68 V (2.42%)4828.4 WDrop High
150 mm²309 A241 A4.7 V (1.17%)395.3 V7.74 V (1.94%)3862.7 WDrop High
185 mm²353 A275 A3.81 V (0.95%)396.2 V6.28 V (1.57%)3131.9 WDrop High
240 mm²415 A324 A2.93 V (0.73%)397.1 V4.84 V (1.21%)2414.2 WDrop High
300 mm²477 A372 A2.35 V (0.59%)397.7 V3.87 V (0.97%)1931.3 W✓ OK (≤3%)
400 mm²570 A445 A1.76 V (0.44%)398.2 V2.9 V (0.73%)1448.5 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 475 Ampere bei 40 Meter (400V)

Welcher Kabelquerschnitt wird für 475A bei 40m (400V) benötigt?

Für 475 Ampere über 40 Meter bei 400V wird ein Kupferkabel von 300 mm² empfohlen, um den Spannungsfall unter 3% (2.35V bzw. 0.59%) zu halten.

Wie hoch ist die maximale Leistung bei 475A und 400V?

Die übertragbare Leistung beträgt 329.09 kW bei einer empfohlenen Absicherung von 500A.