Kabelquerschnitt für 600 Ampere bei 120 Meter (230V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 600 A über 120 m einfache Leitungslänge bei 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 3.85V (1.68%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 12.71V (5.53%)
Voltage at Load226.2 VLine Loss: 2311.2 W
Max Power & Breaker138.0 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2054.4 V (893.22%)0.0 V3388.8 V (1473.39%)1232640.0 WDrop High
2.5 mm²24 A18 A1232.64 V (535.93%)0.0 V2033.28 V (884.03%)739584.0 WDrop High
4 mm²32 A25 A770.4 V (334.96%)0.0 V1270.8 V (552.52%)462240.0 WDrop High
6 mm²41 A32 A513.6 V (223.3%)0.0 V847.2 V (368.35%)308160.0 WDrop High
10 mm²57 A44 A308.16 V (133.98%)0.0 V508.32 V (221.01%)184896.0 WDrop High
16 mm²76 A59 A192.6 V (83.74%)37.4 V317.7 V (138.13%)115560.0 WDrop High
25 mm²101 A78 A123.26 V (53.59%)106.7 V203.33 V (88.4%)73958.4 WDrop High
35 mm²125 A97 A88.05 V (38.28%)142.0 V145.23 V (63.15%)52827.4 WDrop High
50 mm²151 A118 A61.63 V (26.8%)168.4 V101.66 V (44.2%)36979.2 WDrop High
70 mm²192 A150 A44.02 V (19.14%)186.0 V72.62 V (31.57%)26413.7 WDrop High
95 mm²232 A181 A32.44 V (14.1%)197.6 V53.51 V (23.26%)19462.7 WDrop High
120 mm²269 A210 A25.68 V (11.17%)204.3 V42.36 V (18.42%)15408.0 WDrop High
150 mm²309 A241 A20.54 V (8.93%)209.5 V33.89 V (14.73%)12326.4 WDrop High
185 mm²353 A275 A16.66 V (7.24%)213.3 V27.48 V (11.95%)9994.4 WDrop High
240 mm²415 A324 A12.84 V (5.58%)217.2 V21.18 V (9.21%)7704.0 WDrop High
300 mm²477 A372 A10.27 V (4.47%)219.7 V16.94 V (7.37%)6163.2 WDrop High
400 mm²570 A445 A7.7 V (3.35%)222.3 V12.71 V (5.53%)4622.4 WDrop High

FAQ — Kabelquerschnitt für 600 Ampere bei 120 Meter (230V)

Welcher Kabelquerschnitt wird für 600A bei 120m (230V) benötigt?

Für 600 Ampere über 120 Meter bei 230V wird ein Kupferkabel von 2× 400 mm² empfohlen, um den Spannungsfall unter 3% (3.85V bzw. 1.68%) zu halten.

Wie hoch ist die maximale Leistung bei 600A und 230V?

Die übertragbare Leistung beträgt 138.0 kW bei einer empfohlenen Absicherung von 600A.