Kabelquerschnitt für 600 Ampere bei 400 Meter (230V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 600 A über 400 m einfache Leitungslänge bei 230V.

Copper Cable (≤3% Drop)4× 400 mm²Drop: 6.42V (2.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 42.36V (18.42%)
Voltage at Load223.6 VLine Loss: 3852.0 W
Max Power & Breaker138.0 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6848.0 V (2977.39%)0.0 V11296.0 V (4911.3%)4108800.0 WDrop High
2.5 mm²24 A18 A4108.8 V (1786.43%)0.0 V6777.6 V (2946.78%)2465280.0 WDrop High
4 mm²32 A25 A2568.0 V (1116.52%)0.0 V4236.0 V (1841.74%)1540800.0 WDrop High
6 mm²41 A32 A1712.0 V (744.35%)0.0 V2824.0 V (1227.83%)1027200.0 WDrop High
10 mm²57 A44 A1027.2 V (446.61%)0.0 V1694.4 V (736.7%)616320.0 WDrop High
16 mm²76 A59 A642.0 V (279.13%)0.0 V1059.0 V (460.43%)385200.0 WDrop High
25 mm²101 A78 A410.88 V (178.64%)0.0 V677.76 V (294.68%)246528.0 WDrop High
35 mm²125 A97 A293.49 V (127.6%)0.0 V484.11 V (210.48%)176091.4 WDrop High
50 mm²151 A118 A205.44 V (89.32%)24.6 V338.88 V (147.34%)123264.0 WDrop High
70 mm²192 A150 A146.74 V (63.8%)83.3 V242.06 V (105.24%)88045.7 WDrop High
95 mm²232 A181 A108.13 V (47.01%)121.9 V178.36 V (77.55%)64875.8 WDrop High
120 mm²269 A210 A85.6 V (37.22%)144.4 V141.2 V (61.39%)51360.0 WDrop High
150 mm²309 A241 A68.48 V (29.77%)161.5 V112.96 V (49.11%)41088.0 WDrop High
185 mm²353 A275 A55.52 V (24.14%)174.5 V91.59 V (39.82%)33314.6 WDrop High
240 mm²415 A324 A42.8 V (18.61%)187.2 V70.6 V (30.7%)25680.0 WDrop High
300 mm²477 A372 A34.24 V (14.89%)195.8 V56.48 V (24.56%)20544.0 WDrop High
400 mm²570 A445 A25.68 V (11.17%)204.3 V42.36 V (18.42%)15408.0 WDrop High

FAQ — Kabelquerschnitt für 600 Ampere bei 400 Meter (230V)

Welcher Kabelquerschnitt wird für 600A bei 400m (230V) benötigt?

Für 600 Ampere über 400 Meter bei 230V wird ein Kupferkabel von 4× 400 mm² empfohlen, um den Spannungsfall unter 3% (6.42V bzw. 2.79%) zu halten.

Wie hoch ist die maximale Leistung bei 600A und 230V?

Die übertragbare Leistung beträgt 138.0 kW bei einer empfohlenen Absicherung von 600A.