Kabelquerschnitt für 650 Ampere bei 50 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 650 A über 50 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.5V (0.38%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.97V (1.24%)
Voltage at Load398.5 VLine Loss: 1695.3 W
Max Power & Breaker450.33 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 650A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A803.09 V (200.77%)0.0 V1324.73 V (331.18%)904150.0 WDrop High
2.5 mm²24 A18 A481.86 V (120.46%)0.0 V794.84 V (198.71%)542490.0 WDrop High
4 mm²32 A25 A301.16 V (75.29%)98.8 V496.77 V (124.19%)339056.2 WDrop High
6 mm²41 A32 A200.77 V (50.19%)199.2 V331.18 V (82.8%)226037.5 WDrop High
10 mm²57 A44 A120.46 V (30.12%)279.5 V198.71 V (49.68%)135622.5 WDrop High
16 mm²76 A59 A75.29 V (18.82%)324.7 V124.19 V (31.05%)84764.1 WDrop High
25 mm²101 A78 A48.19 V (12.05%)351.8 V79.48 V (19.87%)54249.0 WDrop High
35 mm²125 A97 A34.42 V (8.6%)365.6 V56.77 V (14.19%)38749.3 WDrop High
50 mm²151 A118 A24.09 V (6.02%)375.9 V39.74 V (9.94%)27124.5 WDrop High
70 mm²192 A150 A17.21 V (4.3%)382.8 V28.39 V (7.1%)19374.6 WDrop High
95 mm²232 A181 A12.68 V (3.17%)387.3 V20.92 V (5.23%)14276.1 WDrop High
120 mm²269 A210 A10.04 V (2.51%)390.0 V16.56 V (4.14%)11301.9 WDrop High
150 mm²309 A241 A8.03 V (2.01%)392.0 V13.25 V (3.31%)9041.5 WDrop High
185 mm²353 A275 A6.51 V (1.63%)393.5 V10.74 V (2.69%)7330.9 WDrop High
240 mm²415 A324 A5.02 V (1.25%)395.0 V8.28 V (2.07%)5650.9 WDrop High
300 mm²477 A372 A4.02 V (1.0%)396.0 V6.62 V (1.66%)4520.8 WDrop High
400 mm²570 A445 A3.01 V (0.75%)397.0 V4.97 V (1.24%)3390.6 WDrop High

FAQ — Kabelquerschnitt für 650 Ampere bei 50 Meter (400V)

Welcher Kabelquerschnitt wird für 650A bei 50m (400V) benötigt?

Für 650 Ampere über 50 Meter bei 400V wird ein Kupferkabel von 2× 400 mm² empfohlen, um den Spannungsfall unter 3% (1.5V bzw. 0.38%) zu halten.

Wie hoch ist die maximale Leistung bei 650A und 400V?

Die übertragbare Leistung beträgt 450.33 kW bei einer empfohlenen Absicherung von 700A.