Kabelquerschnitt für 750 Ampere bei 80 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 750 A über 80 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 2.78V (0.69%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.17V (2.29%)
Voltage at Load397.2 VLine Loss: 3611.2 W
Max Power & Breaker519.62 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 750A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1482.64 V (370.66%)0.0 V2445.66 V (611.41%)1926000.0 WDrop High
2.5 mm²24 A18 A889.58 V (222.4%)0.0 V1467.39 V (366.85%)1155600.0 WDrop High
4 mm²32 A25 A555.99 V (139.0%)0.0 V917.12 V (229.28%)722250.0 WDrop High
6 mm²41 A32 A370.66 V (92.66%)29.3 V611.41 V (152.85%)481500.0 WDrop High
10 mm²57 A44 A222.4 V (55.6%)177.6 V366.85 V (91.71%)288900.0 WDrop High
16 mm²76 A59 A139.0 V (34.75%)261.0 V229.28 V (57.32%)180562.5 WDrop High
25 mm²101 A78 A88.96 V (22.24%)311.0 V146.74 V (36.68%)115560.0 WDrop High
35 mm²125 A97 A63.54 V (15.89%)336.5 V104.81 V (26.2%)82542.9 WDrop High
50 mm²151 A118 A44.48 V (11.12%)355.5 V73.37 V (18.34%)57780.0 WDrop High
70 mm²192 A150 A31.77 V (7.94%)368.2 V52.41 V (13.1%)41271.4 WDrop High
95 mm²232 A181 A23.41 V (5.85%)376.6 V38.62 V (9.65%)30410.5 WDrop High
120 mm²269 A210 A18.53 V (4.63%)381.5 V30.57 V (7.64%)24075.0 WDrop High
150 mm²309 A241 A14.83 V (3.71%)385.2 V24.46 V (6.11%)19260.0 WDrop High
185 mm²353 A275 A12.02 V (3.01%)388.0 V19.83 V (4.96%)15616.2 WDrop High
240 mm²415 A324 A9.27 V (2.32%)390.7 V15.29 V (3.82%)12037.5 WDrop High
300 mm²477 A372 A7.41 V (1.85%)392.6 V12.23 V (3.06%)9630.0 WDrop High
400 mm²570 A445 A5.56 V (1.39%)394.4 V9.17 V (2.29%)7222.5 WDrop High

FAQ — Kabelquerschnitt für 750 Ampere bei 80 Meter (400V)

Welcher Kabelquerschnitt wird für 750A bei 80m (400V) benötigt?

Für 750 Ampere über 80 Meter bei 400V wird ein Kupferkabel von 2× 400 mm² empfohlen, um den Spannungsfall unter 3% (2.78V bzw. 0.69%) zu halten.

Wie hoch ist die maximale Leistung bei 750A und 400V?

Die übertragbare Leistung beträgt 519.62 kW bei einer empfohlenen Absicherung von 800A.