⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 80 Ampere bei 175 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 80 A über 175 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)50 mm²Drop: 10.38V (2.59%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 9.01V (2.25%)
Voltage at Load389.6 VLine Loss: 1438.1 W
Max Power & Breaker55.43 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A345.95 V (86.49%)54.1 V570.65 V (142.66%)47936.0 WDrop High
2.5 mm²24 A18 A207.57 V (51.89%)192.4 V342.39 V (85.6%)28761.6 WDrop High
4 mm²32 A25 A129.73 V (32.43%)270.3 V213.99 V (53.5%)17976.0 WDrop High
6 mm²41 A32 A86.49 V (21.62%)313.5 V142.66 V (35.67%)11984.0 WDrop High
10 mm²57 A44 A51.89 V (12.97%)348.1 V85.6 V (21.4%)7190.4 WDrop High
16 mm²76 A59 A32.43 V (8.11%)367.6 V53.5 V (13.37%)4494.0 WDrop High
25 mm²101 A78 A20.76 V (5.19%)379.2 V34.24 V (8.56%)2876.2 WDrop High
35 mm²125 A97 A14.83 V (3.71%)385.2 V24.46 V (6.11%)2054.4 W~ ≤5%
50 mm²151 A118 A10.38 V (2.59%)389.6 V17.12 V (4.28%)1438.1 W✓ OK (≤3%)
70 mm²192 A150 A7.41 V (1.85%)392.6 V12.23 V (3.06%)1027.2 W✓ OK (≤3%)
95 mm²232 A181 A5.46 V (1.37%)394.5 V9.01 V (2.25%)756.9 W✓ OK (≤3%)
120 mm²269 A210 A4.32 V (1.08%)395.7 V7.13 V (1.78%)599.2 W✓ OK (≤3%)
150 mm²309 A241 A3.46 V (0.86%)396.5 V5.71 V (1.43%)479.4 W✓ OK (≤3%)
185 mm²353 A275 A2.8 V (0.7%)397.2 V4.63 V (1.16%)388.7 W✓ OK (≤3%)
240 mm²415 A324 A2.16 V (0.54%)397.8 V3.57 V (0.89%)299.6 W✓ OK (≤3%)
300 mm²477 A372 A1.73 V (0.43%)398.3 V2.85 V (0.71%)239.7 W✓ OK (≤3%)
400 mm²570 A445 A1.3 V (0.32%)398.7 V2.14 V (0.53%)179.8 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 80 Ampere bei 175 Meter (400V)

Welcher Kabelquerschnitt wird für 80A bei 175m (400V) benötigt?

Für 80 Ampere über 175 Meter bei 400V wird ein Kupferkabel von 50 mm² empfohlen, um den Spannungsfall unter 3% (10.38V bzw. 2.59%) zu halten.

Wie hoch ist die maximale Leistung bei 80A und 400V?

Die übertragbare Leistung beträgt 55.43 kW bei einer empfohlenen Absicherung von 80A.