Kabelquerschnitt für 800 Ampere bei 40 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 800 A über 40 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.49V (0.37%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.89V (1.22%)
Voltage at Load398.5 VLine Loss: 2054.4 W
Max Power & Breaker554.26 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A790.74 V (197.68%)0.0 V1304.35 V (326.09%)1095680.0 WDrop High
2.5 mm²24 A18 A474.44 V (118.61%)0.0 V782.61 V (195.65%)657408.0 WDrop High
4 mm²32 A25 A296.53 V (74.13%)103.5 V489.13 V (122.28%)410880.0 WDrop High
6 mm²41 A32 A197.68 V (49.42%)202.3 V326.09 V (81.52%)273920.0 WDrop High
10 mm²57 A44 A118.61 V (29.65%)281.4 V195.65 V (48.91%)164352.0 WDrop High
16 mm²76 A59 A74.13 V (18.53%)325.9 V122.28 V (30.57%)102720.0 WDrop High
25 mm²101 A78 A47.44 V (11.86%)352.6 V78.26 V (19.57%)65740.8 WDrop High
35 mm²125 A97 A33.89 V (8.47%)366.1 V55.9 V (13.98%)46957.7 WDrop High
50 mm²151 A118 A23.72 V (5.93%)376.3 V39.13 V (9.78%)32870.4 WDrop High
70 mm²192 A150 A16.94 V (4.24%)383.1 V27.95 V (6.99%)23478.9 WDrop High
95 mm²232 A181 A12.49 V (3.12%)387.5 V20.59 V (5.15%)17300.2 WDrop High
120 mm²269 A210 A9.88 V (2.47%)390.1 V16.3 V (4.08%)13696.0 WDrop High
150 mm²309 A241 A7.91 V (1.98%)392.1 V13.04 V (3.26%)10956.8 WDrop High
185 mm²353 A275 A6.41 V (1.6%)393.6 V10.58 V (2.64%)8883.9 WDrop High
240 mm²415 A324 A4.94 V (1.24%)395.1 V8.15 V (2.04%)6848.0 WDrop High
300 mm²477 A372 A3.95 V (0.99%)396.0 V6.52 V (1.63%)5478.4 WDrop High
400 mm²570 A445 A2.97 V (0.74%)397.0 V4.89 V (1.22%)4108.8 WDrop High

FAQ — Kabelquerschnitt für 800 Ampere bei 40 Meter (400V)

Welcher Kabelquerschnitt wird für 800A bei 40m (400V) benötigt?

Für 800 Ampere über 40 Meter bei 400V wird ein Kupferkabel von 2× 400 mm² empfohlen, um den Spannungsfall unter 3% (1.49V bzw. 0.37%) zu halten.

Wie hoch ist die maximale Leistung bei 800A und 400V?

Die übertragbare Leistung beträgt 554.26 kW bei einer empfohlenen Absicherung von 800A.