Kabelquerschnitt für 800 Ampere bei 500 Meter (230V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 800 A über 500 m einfache Leitungslänge bei 230V.

Copper Cable (≤3% Drop)7× 400 mm²Drop: 6.11V (2.66%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 70.6V (30.7%)
Voltage at Load223.9 VLine Loss: 4891.4 W
Max Power & Breaker184.0 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A11413.33 V (4962.32%)0.0 V18826.67 V (8185.51%)9130666.7 WDrop High
2.5 mm²24 A18 A6848.0 V (2977.39%)0.0 V11296.0 V (4911.3%)5478400.0 WDrop High
4 mm²32 A25 A4280.0 V (1860.87%)0.0 V7060.0 V (3069.57%)3424000.0 WDrop High
6 mm²41 A32 A2853.33 V (1240.58%)0.0 V4706.67 V (2046.38%)2282666.7 WDrop High
10 mm²57 A44 A1712.0 V (744.35%)0.0 V2824.0 V (1227.83%)1369600.0 WDrop High
16 mm²76 A59 A1070.0 V (465.22%)0.0 V1765.0 V (767.39%)856000.0 WDrop High
25 mm²101 A78 A684.8 V (297.74%)0.0 V1129.6 V (491.13%)547840.0 WDrop High
35 mm²125 A97 A489.14 V (212.67%)0.0 V806.86 V (350.81%)391314.3 WDrop High
50 mm²151 A118 A342.4 V (148.87%)0.0 V564.8 V (245.57%)273920.0 WDrop High
70 mm²192 A150 A244.57 V (106.34%)0.0 V403.43 V (175.4%)195657.1 WDrop High
95 mm²232 A181 A180.21 V (78.35%)49.8 V297.26 V (129.24%)144168.4 WDrop High
120 mm²269 A210 A142.67 V (62.03%)87.3 V235.33 V (102.32%)114133.3 WDrop High
150 mm²309 A241 A114.13 V (49.62%)115.9 V188.27 V (81.86%)91306.7 WDrop High
185 mm²353 A275 A92.54 V (40.24%)137.5 V152.65 V (66.37%)74032.4 WDrop High
240 mm²415 A324 A71.33 V (31.01%)158.7 V117.67 V (51.16%)57066.7 WDrop High
300 mm²477 A372 A57.07 V (24.81%)172.9 V94.13 V (40.93%)45653.3 WDrop High
400 mm²570 A445 A42.8 V (18.61%)187.2 V70.6 V (30.7%)34240.0 WDrop High

FAQ — Kabelquerschnitt für 800 Ampere bei 500 Meter (230V)

Welcher Kabelquerschnitt wird für 800A bei 500m (230V) benötigt?

Für 800 Ampere über 500 Meter bei 230V wird ein Kupferkabel von 7× 400 mm² empfohlen, um den Spannungsfall unter 3% (6.11V bzw. 2.66%) zu halten.

Wie hoch ist die maximale Leistung bei 800A und 230V?

Die übertragbare Leistung beträgt 184.0 kW bei einer empfohlenen Absicherung von 800A.