Kabelquerschnitt für 800 Ampere bei 80 Meter (230V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 800 A über 80 m einfache Leitungslänge bei 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 3.42V (1.49%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 11.3V (4.91%)
Voltage at Load226.6 VLine Loss: 2739.2 W
Max Power & Breaker184.0 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1826.13 V (793.97%)0.0 V3012.27 V (1309.68%)1460906.7 WDrop High
2.5 mm²24 A18 A1095.68 V (476.38%)0.0 V1807.36 V (785.81%)876544.0 WDrop High
4 mm²32 A25 A684.8 V (297.74%)0.0 V1129.6 V (491.13%)547840.0 WDrop High
6 mm²41 A32 A456.53 V (198.49%)0.0 V753.07 V (327.42%)365226.7 WDrop High
10 mm²57 A44 A273.92 V (119.1%)0.0 V451.84 V (196.45%)219136.0 WDrop High
16 mm²76 A59 A171.2 V (74.43%)58.8 V282.4 V (122.78%)136960.0 WDrop High
25 mm²101 A78 A109.57 V (47.64%)120.4 V180.74 V (78.58%)87654.4 WDrop High
35 mm²125 A97 A78.26 V (34.03%)151.7 V129.1 V (56.13%)62610.3 WDrop High
50 mm²151 A118 A54.78 V (23.82%)175.2 V90.37 V (39.29%)43827.2 WDrop High
70 mm²192 A150 A39.13 V (17.01%)190.9 V64.55 V (28.06%)31305.1 WDrop High
95 mm²232 A181 A28.83 V (12.54%)201.2 V47.56 V (20.68%)23066.9 WDrop High
120 mm²269 A210 A22.83 V (9.92%)207.2 V37.65 V (16.37%)18261.3 WDrop High
150 mm²309 A241 A18.26 V (7.94%)211.7 V30.12 V (13.1%)14609.1 WDrop High
185 mm²353 A275 A14.81 V (6.44%)215.2 V24.42 V (10.62%)11845.2 WDrop High
240 mm²415 A324 A11.41 V (4.96%)218.6 V18.83 V (8.19%)9130.7 WDrop High
300 mm²477 A372 A9.13 V (3.97%)220.9 V15.06 V (6.55%)7304.5 WDrop High
400 mm²570 A445 A6.85 V (2.98%)223.2 V11.3 V (4.91%)5478.4 WDrop High

FAQ — Kabelquerschnitt für 800 Ampere bei 80 Meter (230V)

Welcher Kabelquerschnitt wird für 800A bei 80m (230V) benötigt?

Für 800 Ampere über 80 Meter bei 230V wird ein Kupferkabel von 2× 400 mm² empfohlen, um den Spannungsfall unter 3% (3.42V bzw. 1.49%) zu halten.

Wie hoch ist die maximale Leistung bei 800A und 230V?

Die übertragbare Leistung beträgt 184.0 kW bei einer empfohlenen Absicherung von 800A.