Kabelquerschnitt für 900 Ampere bei 120 Meter (230V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 900 A über 120 m einfache Leitungslänge bei 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 5.78V (2.51%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 19.06V (8.29%)
Voltage at Load224.2 VLine Loss: 5200.2 W
Max Power & Breaker207.0 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3081.6 V (1339.83%)0.0 V5083.2 V (2210.09%)2773440.0 WDrop High
2.5 mm²24 A18 A1848.96 V (803.9%)0.0 V3049.92 V (1326.05%)1664064.0 WDrop High
4 mm²32 A25 A1155.6 V (502.43%)0.0 V1906.2 V (828.78%)1040040.0 WDrop High
6 mm²41 A32 A770.4 V (334.96%)0.0 V1270.8 V (552.52%)693360.0 WDrop High
10 mm²57 A44 A462.24 V (200.97%)0.0 V762.48 V (331.51%)416016.0 WDrop High
16 mm²76 A59 A288.9 V (125.61%)0.0 V476.55 V (207.2%)260010.0 WDrop High
25 mm²101 A78 A184.9 V (80.39%)45.1 V304.99 V (132.61%)166406.4 WDrop High
35 mm²125 A97 A132.07 V (57.42%)97.9 V217.85 V (94.72%)118861.7 WDrop High
50 mm²151 A118 A92.45 V (40.19%)137.6 V152.5 V (66.3%)83203.2 WDrop High
70 mm²192 A150 A66.03 V (28.71%)164.0 V108.93 V (47.36%)59430.9 WDrop High
95 mm²232 A181 A48.66 V (21.16%)181.3 V80.26 V (34.9%)43791.2 WDrop High
120 mm²269 A210 A38.52 V (16.75%)191.5 V63.54 V (27.63%)34668.0 WDrop High
150 mm²309 A241 A30.82 V (13.4%)199.2 V50.83 V (22.1%)27734.4 WDrop High
185 mm²353 A275 A24.99 V (10.86%)205.0 V41.22 V (17.92%)22487.4 WDrop High
240 mm²415 A324 A19.26 V (8.37%)210.7 V31.77 V (13.81%)17334.0 WDrop High
300 mm²477 A372 A15.41 V (6.7%)214.6 V25.42 V (11.05%)13867.2 WDrop High
400 mm²570 A445 A11.56 V (5.02%)218.4 V19.06 V (8.29%)10400.4 WDrop High

FAQ — Kabelquerschnitt für 900 Ampere bei 120 Meter (230V)

Welcher Kabelquerschnitt wird für 900A bei 120m (230V) benötigt?

Für 900 Ampere über 120 Meter bei 230V wird ein Kupferkabel von 2× 400 mm² empfohlen, um den Spannungsfall unter 3% (5.78V bzw. 2.51%) zu halten.

Wie hoch ist die maximale Leistung bei 900A und 230V?

Die übertragbare Leistung beträgt 207.0 kW bei einer empfohlenen Absicherung von 1000A.