🏭 Industrial Electrical Conversion · Three-Phase & Single-Phase

1 kVA to Amps at 120V Single-Phase AC

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 1 kVA on a 120V Single-Phase AC circuit.

Line Current (0.85 PF)8.33 AAt 1.0 PF: 8.33 A
Active / Apparent Power0.85 kW1.0 kVA · 0.53 kVAR
Recommended Breaker13 A (NEC)10 A (IEC Nominal)
Recommended Copper Wire14 AWGIEC Metric: 2.5 mm²

Engineering Breakdown for 1 kVA at 120V

Input Rating1 kVA (120V Single-Phase AC)
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)8.33 Amps
Amperage at 1.00 Power Factor (Resistive Load)8.33 Amps
Real Power (kW / Watts)0.85 kW (850 W)
Apparent Power (kVA) & Reactive Power (kVAR)1.0 kVA / 0.53 kVAR
Equivalent Mechanical Horsepower (HP)1.14 HP
NEC 125% Continuous Circuit Breaker13 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)14 AWG (NEC) / 2.5 mm² (IEC)

Frequently Asked Questions

How many amps is 1 kVA at 120V (1-Phase)?

At 120V Single-Phase AC, 1 kVA equals 8.33 Amps at an industrial power factor of 0.85 (or 8.33 Amps at unity power factor 1.0).

What size breaker and wire is needed for 1 kVA at 120V?

For 8.33A continuous load, NEC requires a 125% rated breaker of 13A with 14 AWG copper conductors, while IEC standard sizing uses a 10A breaker with 2.5 mm² copper cable.