126 kVA to Amps at 600V Three-Phase AC (Canada / Heavy)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 126 kVA on a 600V Three-Phase AC (Canada / Heavy) circuit.

Line Current (0.85 PF)121.24 AAt 1.0 PF: 121.24 A
Active / Apparent Power107.1 kW126.0 kVA · 66.37 kVAR
Recommended Breaker160 A (NEC)125 A (IEC Nominal)
Recommended Copper Wire1 AWGIEC Metric: 35 mm²

Engineering Breakdown for 126 kVA at 600V

Input Rating126 kVA (600V Three-Phase AC (Canada / Heavy))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)121.24 Amps
Amperage at 1.00 Power Factor (Resistive Load)121.24 Amps
Real Power (kW / Watts)107.1 kW (107,100 W)
Apparent Power (kVA) & Reactive Power (kVAR)126.0 kVA / 66.37 kVAR
Equivalent Mechanical Horsepower (HP)143.62 HP
NEC 125% Continuous Circuit Breaker160 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)1 AWG (NEC) / 35 mm² (IEC)

Frequently Asked Questions

How many amps is 126 kVA at 600V (3-Phase)?

At 600V Three-Phase AC (Canada / Heavy), 126 kVA equals 121.24 Amps at an industrial power factor of 0.85 (or 121.24 Amps at unity power factor 1.0).

What size breaker and wire is needed for 126 kVA at 600V?

For 121.24A continuous load, NEC requires a 125% rated breaker of 160A with 1 AWG copper conductors, while IEC standard sizing uses a 125A breaker with 35 mm² copper cable.