134 kVA to Amps at 600V Three-Phase AC (Canada / Heavy)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 134 kVA on a 600V Three-Phase AC (Canada / Heavy) circuit.

Line Current (0.85 PF)128.94 AAt 1.0 PF: 128.94 A
Active / Apparent Power113.9 kW134.0 kVA · 70.59 kVAR
Recommended Breaker175 A (NEC)150 A (IEC Nominal)
Recommended Copper Wire1 AWGIEC Metric: 50 mm²

Engineering Breakdown for 134 kVA at 600V

Input Rating134 kVA (600V Three-Phase AC (Canada / Heavy))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)128.94 Amps
Amperage at 1.00 Power Factor (Resistive Load)128.94 Amps
Real Power (kW / Watts)113.9 kW (113,900 W)
Apparent Power (kVA) & Reactive Power (kVAR)134.0 kVA / 70.59 kVAR
Equivalent Mechanical Horsepower (HP)152.74 HP
NEC 125% Continuous Circuit Breaker175 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)1 AWG (NEC) / 50 mm² (IEC)

Frequently Asked Questions

How many amps is 134 kVA at 600V (3-Phase)?

At 600V Three-Phase AC (Canada / Heavy), 134 kVA equals 128.94 Amps at an industrial power factor of 0.85 (or 128.94 Amps at unity power factor 1.0).

What size breaker and wire is needed for 134 kVA at 600V?

For 128.94A continuous load, NEC requires a 125% rated breaker of 175A with 1 AWG copper conductors, while IEC standard sizing uses a 150A breaker with 50 mm² copper cable.