172 kVA to Amps at 600V Three-Phase AC (Canada / Heavy)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 172 kVA on a 600V Three-Phase AC (Canada / Heavy) circuit.

Line Current (0.85 PF)165.51 AAt 1.0 PF: 165.51 A
Active / Apparent Power146.2 kW172.0 kVA · 90.61 kVAR
Recommended Breaker225 A (NEC)175 A (IEC Nominal)
Recommended Copper Wire2/0 AWGIEC Metric: 70 mm²

Engineering Breakdown for 172 kVA at 600V

Input Rating172 kVA (600V Three-Phase AC (Canada / Heavy))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)165.51 Amps
Amperage at 1.00 Power Factor (Resistive Load)165.51 Amps
Real Power (kW / Watts)146.2 kW (146,200 W)
Apparent Power (kVA) & Reactive Power (kVAR)172.0 kVA / 90.61 kVAR
Equivalent Mechanical Horsepower (HP)196.06 HP
NEC 125% Continuous Circuit Breaker225 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)2/0 AWG (NEC) / 70 mm² (IEC)

Frequently Asked Questions

How many amps is 172 kVA at 600V (3-Phase)?

At 600V Three-Phase AC (Canada / Heavy), 172 kVA equals 165.51 Amps at an industrial power factor of 0.85 (or 165.51 Amps at unity power factor 1.0).

What size breaker and wire is needed for 172 kVA at 600V?

For 165.51A continuous load, NEC requires a 125% rated breaker of 225A with 2/0 AWG copper conductors, while IEC standard sizing uses a 175A breaker with 70 mm² copper cable.