⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
🏭 Industrial Electrical Conversion · Three-Phase & Single-Phase

180 kVA to Amps at 600V Three-Phase AC (Canada / Heavy)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 180 kVA on a 600V Three-Phase AC (Canada / Heavy) circuit.

Line Current (0.85 PF)173.21 AAt 1.0 PF: 173.21 A
Active / Apparent Power153.0 kW180.0 kVA · 94.82 kVAR
Recommended Breaker225 A (NEC)175 A (IEC Nominal)
Recommended Copper Wire2/0 AWGIEC Metric: 70 mm²

Engineering Breakdown for 180 kVA at 600V

Input Rating180 kVA (600V Three-Phase AC (Canada / Heavy))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)173.21 Amps
Amperage at 1.00 Power Factor (Resistive Load)173.21 Amps
Real Power (kW / Watts)153.0 kW (153,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)180.0 kVA / 94.82 kVAR
Equivalent Mechanical Horsepower (HP)205.18 HP
NEC 125% Continuous Circuit Breaker225 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)2/0 AWG (NEC) / 70 mm² (IEC)

Frequently Asked Questions

How many amps is 180 kVA at 600V (3-Phase)?

At 600V Three-Phase AC (Canada / Heavy), 180 kVA equals 173.21 Amps at an industrial power factor of 0.85 (or 173.21 Amps at unity power factor 1.0).

What size breaker and wire is needed for 180 kVA at 600V?

For 173.21A continuous load, NEC requires a 125% rated breaker of 225A with 2/0 AWG copper conductors, while IEC standard sizing uses a 175A breaker with 70 mm² copper cable.