218 kVA to Amps at 120V Single-Phase AC
Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 218 kVA on a 120V Single-Phase AC circuit.
Line Current (0.85 PF)1816.67 AAt 1.0 PF: 1816.67 A
Active / Apparent Power185.3 kW218.0 kVA · 114.84 kVAR
Recommended Breaker2500 A (NEC)2000 A (IEC Nominal)
Recommended Copper Wire4× 1000 kcmil (Parallel)IEC Metric: 4× 400 mm²
Engineering Breakdown for 218 kVA at 120V
| Input Rating | 218 kVA (120V Single-Phase AC) |
| Amperage at 0.85 Power Factor (Industrial Motor/Transformer) | 1816.67 Amps |
| Amperage at 1.00 Power Factor (Resistive Load) | 1816.67 Amps |
| Real Power (kW / Watts) | 185.3 kW (185,300 W) |
| Apparent Power (kVA) & Reactive Power (kVAR) | 218.0 kVA / 114.84 kVAR |
| Equivalent Mechanical Horsepower (HP) | 248.49 HP |
| NEC 125% Continuous Circuit Breaker | 2500 A |
| Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop) | 4× 1000 kcmil (Parallel) (NEC) / 4× 400 mm² (IEC) |
Frequently Asked Questions
How many amps is 218 kVA at 120V (1-Phase)?
At 120V Single-Phase AC, 218 kVA equals 1816.67 Amps at an industrial power factor of 0.85 (or 1816.67 Amps at unity power factor 1.0).
What size breaker and wire is needed for 218 kVA at 120V?
For 1816.67A continuous load, NEC requires a 125% rated breaker of 2500A with 4× 1000 kcmil (Parallel) copper conductors, while IEC standard sizing uses a 2000A breaker with 4× 400 mm² copper cable.
Other Power Ratings & Voltages
5 kVA at 120V (1P)10 kVA at 120V (1P)15 kVA at 120V (1P)20 kVA at 120V (1P)25 kVA at 120V (1P)30 kVA at 120V (1P)45 kVA at 120V (1P)50 kVA at 120V (1P)75 kVA at 120V (1P)100 kVA at 120V (1P)150 kVA at 120V (1P)200 kVA at 120V (1P)250 kVA at 120V (1P)500 kVA at 120V (1P)218 kVA at 208V Single-Phase AC218 kVA at 230V Single-Phase AC (IEC)218 kVA at 240V Single-Phase AC (NEC)218 kVA at 208V Three-Phase AC218 kVA at 230V Three-Phase AC218 kVA at 400V Three-Phase AC (IEC Europe)218 kVA at 415V Three-Phase AC (UK / AU)218 kVA at 480V Three-Phase AC (US Industrial)218 kVA at 600V Three-Phase AC (Canada / Heavy)218 kVA at 24V DC Direct Current218 kVA at 48V DC Battery / Telecom Bus