42 kVA to Amps at 600V Three-Phase AC (Canada / Heavy)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 42 kVA on a 600V Three-Phase AC (Canada / Heavy) circuit.

Line Current (0.85 PF)40.41 AAt 1.0 PF: 40.41 A
Active / Apparent Power35.7 kW42.0 kVA · 22.12 kVAR
Recommended Breaker60 A (NEC)45 A (IEC Nominal)
Recommended Copper Wire8 AWGIEC Metric: 6 mm²

Engineering Breakdown for 42 kVA at 600V

Input Rating42 kVA (600V Three-Phase AC (Canada / Heavy))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)40.41 Amps
Amperage at 1.00 Power Factor (Resistive Load)40.41 Amps
Real Power (kW / Watts)35.7 kW (35,700 W)
Apparent Power (kVA) & Reactive Power (kVAR)42.0 kVA / 22.12 kVAR
Equivalent Mechanical Horsepower (HP)47.87 HP
NEC 125% Continuous Circuit Breaker60 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)8 AWG (NEC) / 6 mm² (IEC)

Frequently Asked Questions

How many amps is 42 kVA at 600V (3-Phase)?

At 600V Three-Phase AC (Canada / Heavy), 42 kVA equals 40.41 Amps at an industrial power factor of 0.85 (or 40.41 Amps at unity power factor 1.0).

What size breaker and wire is needed for 42 kVA at 600V?

For 40.41A continuous load, NEC requires a 125% rated breaker of 60A with 8 AWG copper conductors, while IEC standard sizing uses a 45A breaker with 6 mm² copper cable.