420 kVA to Amps at 600V Three-Phase AC (Canada / Heavy)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 420 kVA on a 600V Three-Phase AC (Canada / Heavy) circuit.

Line Current (0.85 PF)404.15 AAt 1.0 PF: 404.15 A
Active / Apparent Power357.0 kW420.0 kVA · 221.25 kVAR
Recommended Breaker600 A (NEC)450 A (IEC Nominal)
Recommended Copper Wire600 kcmilIEC Metric: 240 mm²

Engineering Breakdown for 420 kVA at 600V

Input Rating420 kVA (600V Three-Phase AC (Canada / Heavy))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)404.15 Amps
Amperage at 1.00 Power Factor (Resistive Load)404.15 Amps
Real Power (kW / Watts)357.0 kW (357,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)420.0 kVA / 221.25 kVAR
Equivalent Mechanical Horsepower (HP)478.74 HP
NEC 125% Continuous Circuit Breaker600 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)600 kcmil (NEC) / 240 mm² (IEC)

Frequently Asked Questions

How many amps is 420 kVA at 600V (3-Phase)?

At 600V Three-Phase AC (Canada / Heavy), 420 kVA equals 404.15 Amps at an industrial power factor of 0.85 (or 404.15 Amps at unity power factor 1.0).

What size breaker and wire is needed for 420 kVA at 600V?

For 404.15A continuous load, NEC requires a 125% rated breaker of 600A with 600 kcmil copper conductors, while IEC standard sizing uses a 450A breaker with 240 mm² copper cable.