470 kVA to Amps at 600V Three-Phase AC (Canada / Heavy)
Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 470 kVA on a 600V Three-Phase AC (Canada / Heavy) circuit.
Line Current (0.85 PF)452.26 AAt 1.0 PF: 452.26 A
Active / Apparent Power399.5 kW470.0 kVA · 247.59 kVAR
Recommended Breaker600 A (NEC)500 A (IEC Nominal)
Recommended Copper Wire750 kcmilIEC Metric: 300 mm²
Engineering Breakdown for 470 kVA at 600V
| Input Rating | 470 kVA (600V Three-Phase AC (Canada / Heavy)) |
| Amperage at 0.85 Power Factor (Industrial Motor/Transformer) | 452.26 Amps |
| Amperage at 1.00 Power Factor (Resistive Load) | 452.26 Amps |
| Real Power (kW / Watts) | 399.5 kW (399,500 W) |
| Apparent Power (kVA) & Reactive Power (kVAR) | 470.0 kVA / 247.59 kVAR |
| Equivalent Mechanical Horsepower (HP) | 535.74 HP |
| NEC 125% Continuous Circuit Breaker | 600 A |
| Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop) | 750 kcmil (NEC) / 300 mm² (IEC) |
Frequently Asked Questions
How many amps is 470 kVA at 600V (3-Phase)?
At 600V Three-Phase AC (Canada / Heavy), 470 kVA equals 452.26 Amps at an industrial power factor of 0.85 (or 452.26 Amps at unity power factor 1.0).
What size breaker and wire is needed for 470 kVA at 600V?
For 452.26A continuous load, NEC requires a 125% rated breaker of 600A with 750 kcmil copper conductors, while IEC standard sizing uses a 500A breaker with 300 mm² copper cable.
Other Power Ratings & Voltages
5 kVA at 600V (3P)10 kVA at 600V (3P)15 kVA at 600V (3P)20 kVA at 600V (3P)25 kVA at 600V (3P)30 kVA at 600V (3P)45 kVA at 600V (3P)50 kVA at 600V (3P)75 kVA at 600V (3P)100 kVA at 600V (3P)150 kVA at 600V (3P)200 kVA at 600V (3P)250 kVA at 600V (3P)500 kVA at 600V (3P)470 kVA at 120V Single-Phase AC470 kVA at 208V Single-Phase AC470 kVA at 230V Single-Phase AC (IEC)470 kVA at 240V Single-Phase AC (NEC)470 kVA at 208V Three-Phase AC470 kVA at 230V Three-Phase AC470 kVA at 400V Three-Phase AC (IEC Europe)470 kVA at 415V Three-Phase AC (UK / AU)470 kVA at 480V Three-Phase AC (US Industrial)470 kVA at 24V DC Direct Current470 kVA at 48V DC Battery / Telecom Bus