⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🏭 Industrial Electrical Conversion · Three-Phase & Single-Phase

5.5 kVA to Amps at 230V Three-Phase AC

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 5.5 kVA on a 230V Three-Phase AC circuit.

Line Current (0.85 PF)13.81 AAt 1.0 PF: 13.81 A
Active / Apparent Power4.67 kW5.5 kVA · 2.9 kVAR
Recommended Breaker20 A (NEC)15 A (IEC Nominal)
Recommended Copper Wire14 AWGIEC Metric: 1.5 mm²

Engineering Breakdown for 5.5 kVA at 230V

Input Rating5.5 kVA (230V Three-Phase AC)
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)13.81 Amps
Amperage at 1.00 Power Factor (Resistive Load)13.81 Amps
Real Power (kW / Watts)4.67 kW (4,675 W)
Apparent Power (kVA) & Reactive Power (kVAR)5.5 kVA / 2.9 kVAR
Equivalent Mechanical Horsepower (HP)6.27 HP
NEC 125% Continuous Circuit Breaker20 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)14 AWG (NEC) / 1.5 mm² (IEC)

Frequently Asked Questions

How many amps is 5.5 kVA at 230V (3-Phase)?

At 230V Three-Phase AC, 5.5 kVA equals 13.81 Amps at an industrial power factor of 0.85 (or 13.81 Amps at unity power factor 1.0).

What size breaker and wire is needed for 5.5 kVA at 230V?

For 13.81A continuous load, NEC requires a 125% rated breaker of 20A with 14 AWG copper conductors, while IEC standard sizing uses a 15A breaker with 1.5 mm² copper cable.