9 kVA to Amps at 600V Three-Phase AC (Canada / Heavy)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 9 kVA on a 600V Three-Phase AC (Canada / Heavy) circuit.

Line Current (0.85 PF)8.66 AAt 1.0 PF: 8.66 A
Active / Apparent Power7.65 kW9.0 kVA · 4.74 kVAR
Recommended Breaker13 A (NEC)10 A (IEC Nominal)
Recommended Copper Wire14 AWGIEC Metric: 1.5 mm²

Engineering Breakdown for 9 kVA at 600V

Input Rating9 kVA (600V Three-Phase AC (Canada / Heavy))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)8.66 Amps
Amperage at 1.00 Power Factor (Resistive Load)8.66 Amps
Real Power (kW / Watts)7.65 kW (7,650 W)
Apparent Power (kVA) & Reactive Power (kVAR)9.0 kVA / 4.74 kVAR
Equivalent Mechanical Horsepower (HP)10.26 HP
NEC 125% Continuous Circuit Breaker13 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)14 AWG (NEC) / 1.5 mm² (IEC)

Frequently Asked Questions

How many amps is 9 kVA at 600V (3-Phase)?

At 600V Three-Phase AC (Canada / Heavy), 9 kVA equals 8.66 Amps at an industrial power factor of 0.85 (or 8.66 Amps at unity power factor 1.0).

What size breaker and wire is needed for 9 kVA at 600V?

For 8.66A continuous load, NEC requires a 125% rated breaker of 13A with 14 AWG copper conductors, while IEC standard sizing uses a 10A breaker with 1.5 mm² copper cable.