🏭 Industrial Electrical Conversion · Three-Phase & Single-Phase

100 kW to Amps at 480V Three-Phase AC (US Industrial)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 100 kW on a 480V Three-Phase AC (US Industrial) circuit.

Line Current (0.85 PF)141.51 AAt 1.0 PF: 120.28 A
Active / Apparent Power100.0 kW117.65 kVA · 61.97 kVAR
Recommended Breaker200 A (NEC)150 A (IEC Nominal)
Recommended Copper Wire1/0 AWGIEC Metric: 50 mm²

Engineering Breakdown for 100 kW at 480V

Input Rating100 kW (480V Three-Phase AC (US Industrial))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)141.51 Amps
Amperage at 1.00 Power Factor (Resistive Load)120.28 Amps
Real Power (kW / Watts)100.0 kW (100,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)117.65 kVA / 61.97 kVAR
Equivalent Mechanical Horsepower (HP)134.1 HP
NEC 125% Continuous Circuit Breaker200 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)1/0 AWG (NEC) / 50 mm² (IEC)

Frequently Asked Questions

How many amps is 100 kW at 480V (3-Phase)?

At 480V Three-Phase AC (US Industrial), 100 kW equals 141.51 Amps at an industrial power factor of 0.85 (or 120.28 Amps at unity power factor 1.0).

What size breaker and wire is needed for 100 kW at 480V?

For 141.51A continuous load, NEC requires a 125% rated breaker of 200A with 1/0 AWG copper conductors, while IEC standard sizing uses a 150A breaker with 50 mm² copper cable.