11 kW to Amps at 208V Three-Phase AC

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 11 kW on a 208V Three-Phase AC circuit.

Line Current (0.85 PF)35.92 AAt 1.0 PF: 30.53 A
Active / Apparent Power11.0 kW12.94 kVA · 6.82 kVAR
Recommended Breaker45 A (NEC)40 A (IEC Nominal)
Recommended Copper Wire8 AWGIEC Metric: 6 mm²

Engineering Breakdown for 11 kW at 208V

Input Rating11 kW (208V Three-Phase AC)
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)35.92 Amps
Amperage at 1.00 Power Factor (Resistive Load)30.53 Amps
Real Power (kW / Watts)11.0 kW (11,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)12.94 kVA / 6.82 kVAR
Equivalent Mechanical Horsepower (HP)14.75 HP
NEC 125% Continuous Circuit Breaker45 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)8 AWG (NEC) / 6 mm² (IEC)

Frequently Asked Questions

How many amps is 11 kW at 208V (3-Phase)?

At 208V Three-Phase AC, 11 kW equals 35.92 Amps at an industrial power factor of 0.85 (or 30.53 Amps at unity power factor 1.0).

What size breaker and wire is needed for 11 kW at 208V?

For 35.92A continuous load, NEC requires a 125% rated breaker of 45A with 8 AWG copper conductors, while IEC standard sizing uses a 40A breaker with 6 mm² copper cable.