⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🏭 Industrial Electrical Conversion · Three-Phase & Single-Phase

2 kW to Amps at 120V Single-Phase AC

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 2 kW on a 120V Single-Phase AC circuit.

Line Current (0.85 PF)19.61 AAt 1.0 PF: 16.67 A
Active / Apparent Power2.0 kW2.35 kVA · 1.24 kVAR
Recommended Breaker25 A (NEC)20 A (IEC Nominal)
Recommended Copper Wire10 AWGIEC Metric: 4 mm²

Engineering Breakdown for 2 kW at 120V

Input Rating2 kW (120V Single-Phase AC)
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)19.61 Amps
Amperage at 1.00 Power Factor (Resistive Load)16.67 Amps
Real Power (kW / Watts)2.0 kW (2,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)2.35 kVA / 1.24 kVAR
Equivalent Mechanical Horsepower (HP)2.68 HP
NEC 125% Continuous Circuit Breaker25 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)10 AWG (NEC) / 4 mm² (IEC)

Frequently Asked Questions

How many amps is 2 kW at 120V (1-Phase)?

At 120V Single-Phase AC, 2 kW equals 19.61 Amps at an industrial power factor of 0.85 (or 16.67 Amps at unity power factor 1.0).

What size breaker and wire is needed for 2 kW at 120V?

For 19.61A continuous load, NEC requires a 125% rated breaker of 25A with 10 AWG copper conductors, while IEC standard sizing uses a 20A breaker with 4 mm² copper cable.