240 kW to Amps at 208V Three-Phase AC
Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 240 kW on a 208V Three-Phase AC circuit.
Line Current (0.85 PF)783.73 AAt 1.0 PF: 666.17 A
Active / Apparent Power240.0 kW282.35 kVA · 148.74 kVAR
Recommended Breaker1000 A (NEC)800 A (IEC Nominal)
Recommended Copper Wire2× 1000 kcmil (Parallel)IEC Metric: 2× 400 mm²
Engineering Breakdown for 240 kW at 208V
| Input Rating | 240 kW (208V Three-Phase AC) |
| Amperage at 0.85 Power Factor (Industrial Motor/Transformer) | 783.73 Amps |
| Amperage at 1.00 Power Factor (Resistive Load) | 666.17 Amps |
| Real Power (kW / Watts) | 240.0 kW (240,000 W) |
| Apparent Power (kVA) & Reactive Power (kVAR) | 282.35 kVA / 148.74 kVAR |
| Equivalent Mechanical Horsepower (HP) | 321.85 HP |
| NEC 125% Continuous Circuit Breaker | 1000 A |
| Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop) | 2× 1000 kcmil (Parallel) (NEC) / 2× 400 mm² (IEC) |
Frequently Asked Questions
How many amps is 240 kW at 208V (3-Phase)?
At 208V Three-Phase AC, 240 kW equals 783.73 Amps at an industrial power factor of 0.85 (or 666.17 Amps at unity power factor 1.0).
What size breaker and wire is needed for 240 kW at 208V?
For 783.73A continuous load, NEC requires a 125% rated breaker of 1000A with 2× 1000 kcmil (Parallel) copper conductors, while IEC standard sizing uses a 800A breaker with 2× 400 mm² copper cable.
Other Power Ratings & Voltages
5 kW at 208V (3P)10 kW at 208V (3P)15 kW at 208V (3P)20 kW at 208V (3P)25 kW at 208V (3P)30 kW at 208V (3P)45 kW at 208V (3P)50 kW at 208V (3P)75 kW at 208V (3P)100 kW at 208V (3P)150 kW at 208V (3P)200 kW at 208V (3P)250 kW at 208V (3P)500 kW at 208V (3P)240 kW at 120V Single-Phase AC240 kW at 208V Single-Phase AC240 kW at 230V Single-Phase AC (IEC)240 kW at 240V Single-Phase AC (NEC)240 kW at 230V Three-Phase AC240 kW at 400V Three-Phase AC (IEC Europe)240 kW at 415V Three-Phase AC (UK / AU)240 kW at 480V Three-Phase AC (US Industrial)240 kW at 600V Three-Phase AC (Canada / Heavy)240 kW at 24V DC Direct Current240 kW at 48V DC Battery / Telecom Bus