⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
🏭 Industrial Electrical Conversion · Three-Phase & Single-Phase

5 kW to Amps at 208V Single-Phase AC

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 5 kW on a 208V Single-Phase AC circuit.

Line Current (0.85 PF)28.28 AAt 1.0 PF: 24.04 A
Active / Apparent Power5.0 kW5.88 kVA · 3.1 kVAR
Recommended Breaker40 A (NEC)30 A (IEC Nominal)
Recommended Copper Wire10 AWGIEC Metric: 6 mm²

Engineering Breakdown for 5 kW at 208V

Input Rating5 kW (208V Single-Phase AC)
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)28.28 Amps
Amperage at 1.00 Power Factor (Resistive Load)24.04 Amps
Real Power (kW / Watts)5.0 kW (5,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)5.88 kVA / 3.1 kVAR
Equivalent Mechanical Horsepower (HP)6.71 HP
NEC 125% Continuous Circuit Breaker40 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)10 AWG (NEC) / 6 mm² (IEC)

Frequently Asked Questions

How many amps is 5 kW at 208V (1-Phase)?

At 208V Single-Phase AC, 5 kW equals 28.28 Amps at an industrial power factor of 0.85 (or 24.04 Amps at unity power factor 1.0).

What size breaker and wire is needed for 5 kW at 208V?

For 28.28A continuous load, NEC requires a 125% rated breaker of 40A with 10 AWG copper conductors, while IEC standard sizing uses a 30A breaker with 6 mm² copper cable.