Kabeltverrsnitt for 100 Ampere ved 350 Meter (230V — NEK 400)
Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 100 A over 350 m ved 230V.
Copper Cable (≤3% Drop)240 mm²Drop: 6.24V (2.71%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.18V (2.69%)
Voltage at Load223.8 VLine Loss: 624.2 W
Max Power & Breaker23.0 kW100A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 350m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 998.67 V (434.2%) | 0.0 V | 1647.33 V (716.23%) | 99866.7 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 599.2 V (260.52%) | 0.0 V | 988.4 V (429.74%) | 59920.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 374.5 V (162.83%) | 0.0 V | 617.75 V (268.59%) | 37450.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 249.67 V (108.55%) | 0.0 V | 411.83 V (179.06%) | 24966.7 W | Drop High |
| 10 mm² | 57 A | 44 A | 149.8 V (65.13%) | 80.2 V | 247.1 V (107.43%) | 14980.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 93.62 V (40.71%) | 136.4 V | 154.44 V (67.15%) | 9362.5 W | Drop High |
| 25 mm² | 101 A | 78 A | 59.92 V (26.05%) | 170.1 V | 98.84 V (42.97%) | 5992.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 42.8 V (18.61%) | 187.2 V | 70.6 V (30.7%) | 4280.0 W | Drop High |
| 50 mm² | 151 A | 118 A | 29.96 V (13.03%) | 200.0 V | 49.42 V (21.49%) | 2996.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 21.4 V (9.3%) | 208.6 V | 35.3 V (15.35%) | 2140.0 W | Drop High |
| 95 mm² | 232 A | 181 A | 15.77 V (6.86%) | 214.2 V | 26.01 V (11.31%) | 1576.8 W | Drop High |
| 120 mm² | 269 A | 210 A | 12.48 V (5.43%) | 217.5 V | 20.59 V (8.95%) | 1248.3 W | Drop High |
| 150 mm² | 309 A | 241 A | 9.99 V (4.34%) | 220.0 V | 16.47 V (7.16%) | 998.7 W | ~ ≤5% |
| 185 mm² | 353 A | 275 A | 8.1 V (3.52%) | 221.9 V | 13.36 V (5.81%) | 809.7 W | ~ ≤5% |
| 240 mm² | 415 A | 324 A | 6.24 V (2.71%) | 223.8 V | 10.3 V (4.48%) | 624.2 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 4.99 V (2.17%) | 225.0 V | 8.24 V (3.58%) | 499.3 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 3.74 V (1.63%) | 226.3 V | 6.18 V (2.69%) | 374.5 W | ✓ OK (≤3%) |
FAQ — Kabeltverrsnitt for 100 Ampere ved 350 Meter (230V — NEK 400)
Hvilket kabeltverrsnitt må jeg bruke for 100A over 350 meter (230V)?
Etter NEK 400 anbefales 240 mm² kobberkabel for 100A ved 350 meter (230V), som gir et spenningsfall på 6.24V (2.71%).
Hvor mange kW tåler 100A ved 230V?
Kursen leverer opptil 23.0 kW med 100A vern.
Related Lengths & Currents (230V)
100A · 5m (230V)100A · 10m (230V)100A · 15m (230V)100A · 20m (230V)100A · 25m (230V)100A · 30m (230V)100A · 35m (230V)100A · 40m (230V)100A · 45m (230V)100A · 50m (230V)100A · 60m (230V)100A · 70m (230V)10A · 350m (230V)16A · 350m (230V)20A · 350m (230V)25A · 350m (230V)32A · 350m (230V)40A · 350m (230V)50A · 350m (230V)63A · 350m (230V)80A · 350m (230V)125A · 350m (230V)160A · 350m (230V)200A · 350m (230V)