Kabeltverrsnitt for 110 Ampere ved 200 Meter (230V — NEK 400)
Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 110 A over 200 m ved 230V.
Copper Cable (≤3% Drop)150 mm²Drop: 6.28V (2.73%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 6.47V (2.81%)
Voltage at Load223.7 VLine Loss: 690.5 W
Max Power & Breaker25.3 kW110A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 200m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 627.73 V (272.93%) | 0.0 V | 1035.47 V (450.2%) | 69050.7 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 376.64 V (163.76%) | 0.0 V | 621.28 V (270.12%) | 41430.4 W | Drop High |
| 4 mm² | 32 A | 25 A | 235.4 V (102.35%) | 0.0 V | 388.3 V (168.83%) | 25894.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 156.93 V (68.23%) | 73.1 V | 258.87 V (112.55%) | 17262.7 W | Drop High |
| 10 mm² | 57 A | 44 A | 94.16 V (40.94%) | 135.8 V | 155.32 V (67.53%) | 10357.6 W | Drop High |
| 16 mm² | 76 A | 59 A | 58.85 V (25.59%) | 171.2 V | 97.07 V (42.21%) | 6473.5 W | Drop High |
| 25 mm² | 101 A | 78 A | 37.66 V (16.38%) | 192.3 V | 62.13 V (27.01%) | 4143.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 26.9 V (11.7%) | 203.1 V | 44.38 V (19.29%) | 2959.3 W | Drop High |
| 50 mm² | 151 A | 118 A | 18.83 V (8.19%) | 211.2 V | 31.06 V (13.51%) | 2071.5 W | Drop High |
| 70 mm² | 192 A | 150 A | 13.45 V (5.85%) | 216.5 V | 22.19 V (9.65%) | 1479.7 W | Drop High |
| 95 mm² | 232 A | 181 A | 9.91 V (4.31%) | 220.1 V | 16.35 V (7.11%) | 1090.3 W | ~ ≤5% |
| 120 mm² | 269 A | 210 A | 7.85 V (3.41%) | 222.2 V | 12.94 V (5.63%) | 863.1 W | ~ ≤5% |
| 150 mm² | 309 A | 241 A | 6.28 V (2.73%) | 223.7 V | 10.35 V (4.5%) | 690.5 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 5.09 V (2.21%) | 224.9 V | 8.4 V (3.65%) | 559.9 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 3.92 V (1.71%) | 226.1 V | 6.47 V (2.81%) | 431.6 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 3.14 V (1.36%) | 226.9 V | 5.18 V (2.25%) | 345.3 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 2.35 V (1.02%) | 227.6 V | 3.88 V (1.69%) | 258.9 W | ✓ OK (≤3%) |
FAQ — Kabeltverrsnitt for 110 Ampere ved 200 Meter (230V — NEK 400)
Hvilket kabeltverrsnitt må jeg bruke for 110A over 200 meter (230V)?
Etter NEK 400 anbefales 150 mm² kobberkabel for 110A ved 200 meter (230V), som gir et spenningsfall på 6.28V (2.73%).
Hvor mange kW tåler 110A ved 230V?
Kursen leverer opptil 25.3 kW med 110A vern.
Related Lengths & Currents (230V)
110A · 5m (230V)110A · 10m (230V)110A · 15m (230V)110A · 20m (230V)110A · 25m (230V)110A · 30m (230V)110A · 35m (230V)110A · 40m (230V)110A · 45m (230V)110A · 50m (230V)110A · 60m (230V)110A · 70m (230V)10A · 200m (230V)16A · 200m (230V)20A · 200m (230V)25A · 200m (230V)32A · 200m (230V)40A · 200m (230V)50A · 200m (230V)63A · 200m (230V)80A · 200m (230V)100A · 200m (230V)125A · 200m (230V)160A · 200m (230V)200A · 200m (230V)