Kabeltverrsnitt for 125 Ampere ved 175 Meter (230V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 125 A over 175 m ved 230V.

Copper Cable (≤3% Drop)150 mm²Drop: 6.24V (2.71%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 6.43V (2.8%)
Voltage at Load223.8 VLine Loss: 780.2 W
Max Power & Breaker28.75 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A624.17 V (271.38%)0.0 V1029.58 V (447.64%)78020.8 WDrop High
2.5 mm²24 A18 A374.5 V (162.83%)0.0 V617.75 V (268.59%)46812.5 WDrop High
4 mm²32 A25 A234.06 V (101.77%)0.0 V386.09 V (167.87%)29257.8 WDrop High
6 mm²41 A32 A156.04 V (67.84%)74.0 V257.4 V (111.91%)19505.2 WDrop High
10 mm²57 A44 A93.62 V (40.71%)136.4 V154.44 V (67.15%)11703.1 WDrop High
16 mm²76 A59 A58.52 V (25.44%)171.5 V96.52 V (41.97%)7314.5 WDrop High
25 mm²101 A78 A37.45 V (16.28%)192.6 V61.77 V (26.86%)4681.2 WDrop High
35 mm²125 A97 A26.75 V (11.63%)203.2 V44.12 V (19.18%)3343.7 WDrop High
50 mm²151 A118 A18.72 V (8.14%)211.3 V30.89 V (13.43%)2340.6 WDrop High
70 mm²192 A150 A13.37 V (5.82%)216.6 V22.06 V (9.59%)1671.9 WDrop High
95 mm²232 A181 A9.86 V (4.28%)220.1 V16.26 V (7.07%)1231.9 W~ ≤5%
120 mm²269 A210 A7.8 V (3.39%)222.2 V12.87 V (5.6%)975.3 W~ ≤5%
150 mm²309 A241 A6.24 V (2.71%)223.8 V10.3 V (4.48%)780.2 W✓ OK (≤3%)
185 mm²353 A275 A5.06 V (2.2%)224.9 V8.35 V (3.63%)632.6 W✓ OK (≤3%)
240 mm²415 A324 A3.9 V (1.7%)226.1 V6.43 V (2.8%)487.6 W✓ OK (≤3%)
300 mm²477 A372 A3.12 V (1.36%)226.9 V5.15 V (2.24%)390.1 W✓ OK (≤3%)
400 mm²570 A445 A2.34 V (1.02%)227.7 V3.86 V (1.68%)292.6 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 125 Ampere ved 175 Meter (230V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 125A over 175 meter (230V)?

Etter NEK 400 anbefales 150 mm² kobberkabel for 125A ved 175 meter (230V), som gir et spenningsfall på 6.24V (2.71%).

Hvor mange kW tåler 125A ved 230V?

Kursen leverer opptil 28.75 kW med 125A vern.