Kabeltverrsnitt for 160 Ampere ved 500 Meter (230V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 160 A over 500 m ved 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 4.28V (1.86%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 14.12V (6.14%)
Voltage at Load225.7 VLine Loss: 684.8 W
Max Power & Breaker36.8 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2282.67 V (992.46%)0.0 V3765.33 V (1637.1%)365226.7 WDrop High
2.5 mm²24 A18 A1369.6 V (595.48%)0.0 V2259.2 V (982.26%)219136.0 WDrop High
4 mm²32 A25 A856.0 V (372.17%)0.0 V1412.0 V (613.91%)136960.0 WDrop High
6 mm²41 A32 A570.67 V (248.12%)0.0 V941.33 V (409.28%)91306.7 WDrop High
10 mm²57 A44 A342.4 V (148.87%)0.0 V564.8 V (245.57%)54784.0 WDrop High
16 mm²76 A59 A214.0 V (93.04%)16.0 V353.0 V (153.48%)34240.0 WDrop High
25 mm²101 A78 A136.96 V (59.55%)93.0 V225.92 V (98.23%)21913.6 WDrop High
35 mm²125 A97 A97.83 V (42.53%)132.2 V161.37 V (70.16%)15652.6 WDrop High
50 mm²151 A118 A68.48 V (29.77%)161.5 V112.96 V (49.11%)10956.8 WDrop High
70 mm²192 A150 A48.91 V (21.27%)181.1 V80.69 V (35.08%)7826.3 WDrop High
95 mm²232 A181 A36.04 V (15.67%)194.0 V59.45 V (25.85%)5766.7 WDrop High
120 mm²269 A210 A28.53 V (12.41%)201.5 V47.07 V (20.46%)4565.3 WDrop High
150 mm²309 A241 A22.83 V (9.92%)207.2 V37.65 V (16.37%)3652.3 WDrop High
185 mm²353 A275 A18.51 V (8.05%)211.5 V30.53 V (13.27%)2961.3 WDrop High
240 mm²415 A324 A14.27 V (6.2%)215.7 V23.53 V (10.23%)2282.7 WDrop High
300 mm²477 A372 A11.41 V (4.96%)218.6 V18.83 V (8.19%)1826.1 W~ ≤5%
400 mm²570 A445 A8.56 V (3.72%)221.4 V14.12 V (6.14%)1369.6 W~ ≤5%

FAQ — Kabeltverrsnitt for 160 Ampere ved 500 Meter (230V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 160A over 500 meter (230V)?

Etter NEK 400 anbefales 2× 400 mm² kobberkabel for 160A ved 500 meter (230V), som gir et spenningsfall på 4.28V (1.86%).

Hvor mange kW tåler 160A ved 230V?

Kursen leverer opptil 36.8 kW med 160A vern.