Kabeltverrsnitt for 25 Ampere ved 5 Meter (230V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 25 A over 5 m ved 230V.

Copper Cable (≤3% Drop)4 mm²Drop: 1.34V (0.58%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 2.21V (0.96%)
Voltage at Load228.7 VLine Loss: 33.4 W
Max Power & Breaker5.75 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3.57 V (1.55%)226.4 V5.88 V (2.56%)89.2 WDrop High
2.5 mm²24 A18 A2.14 V (0.93%)227.9 V3.53 V (1.53%)53.5 WDrop High
4 mm²32 A25 A1.34 V (0.58%)228.7 V2.21 V (0.96%)33.4 W✓ OK (≤3%)
6 mm²41 A32 A0.89 V (0.39%)229.1 V1.47 V (0.64%)22.3 W✓ OK (≤3%)
10 mm²57 A44 A0.53 V (0.23%)229.5 V0.88 V (0.38%)13.4 W✓ OK (≤3%)
16 mm²76 A59 A0.33 V (0.15%)229.7 V0.55 V (0.24%)8.4 W✓ OK (≤3%)
25 mm²101 A78 A0.21 V (0.09%)229.8 V0.35 V (0.15%)5.3 W✓ OK (≤3%)
35 mm²125 A97 A0.15 V (0.07%)229.8 V0.25 V (0.11%)3.8 W✓ OK (≤3%)
50 mm²151 A118 A0.11 V (0.05%)229.9 V0.18 V (0.08%)2.7 W✓ OK (≤3%)
70 mm²192 A150 A0.08 V (0.03%)229.9 V0.13 V (0.05%)1.9 W✓ OK (≤3%)
95 mm²232 A181 A0.06 V (0.02%)229.9 V0.09 V (0.04%)1.4 W✓ OK (≤3%)
120 mm²269 A210 A0.04 V (0.02%)230.0 V0.07 V (0.03%)1.1 W✓ OK (≤3%)
150 mm²309 A241 A0.04 V (0.02%)230.0 V0.06 V (0.03%)0.9 W✓ OK (≤3%)
185 mm²353 A275 A0.03 V (0.01%)230.0 V0.05 V (0.02%)0.7 W✓ OK (≤3%)
240 mm²415 A324 A0.02 V (0.01%)230.0 V0.04 V (0.02%)0.6 W✓ OK (≤3%)
300 mm²477 A372 A0.02 V (0.01%)230.0 V0.03 V (0.01%)0.4 W✓ OK (≤3%)
400 mm²570 A445 A0.01 V (0.01%)230.0 V0.02 V (0.01%)0.3 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 25 Ampere ved 5 Meter (230V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 25A over 5 meter (230V)?

Etter NEK 400 anbefales 4 mm² kobberkabel for 25A ved 5 meter (230V), som gir et spenningsfall på 1.34V (0.58%).

Hvor mange kW tåler 25A ved 230V?

Kursen leverer opptil 5.75 kW med 25A vern.