Kabeltverrsnitt for 250 Ampere ved 100 Meter (400V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 250 A over 100 m ved 400V.

Copper Cable (≤3% Drop)120 mm²Drop: 7.72V (1.93%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 8.26V (2.07%)
Voltage at Load392.3 VLine Loss: 3343.7 W
Max Power & Breaker173.21 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A617.76 V (154.44%)0.0 V1019.02 V (254.76%)267500.0 WDrop High
2.5 mm²24 A18 A370.66 V (92.66%)29.3 V611.41 V (152.85%)160500.0 WDrop High
4 mm²32 A25 A231.66 V (57.92%)168.3 V382.13 V (95.53%)100312.5 WDrop High
6 mm²41 A32 A154.44 V (38.61%)245.6 V254.76 V (63.69%)66875.0 WDrop High
10 mm²57 A44 A92.66 V (23.17%)307.3 V152.85 V (38.21%)40125.0 WDrop High
16 mm²76 A59 A57.92 V (14.48%)342.1 V95.53 V (23.88%)25078.1 WDrop High
25 mm²101 A78 A37.07 V (9.27%)362.9 V61.14 V (15.29%)16050.0 WDrop High
35 mm²125 A97 A26.48 V (6.62%)373.5 V43.67 V (10.92%)11464.3 WDrop High
50 mm²151 A118 A18.53 V (4.63%)381.5 V30.57 V (7.64%)8025.0 WDrop High
70 mm²192 A150 A13.24 V (3.31%)386.8 V21.84 V (5.46%)5732.1 WDrop High
95 mm²232 A181 A9.75 V (2.44%)390.2 V16.09 V (4.02%)4223.7 WDrop High
120 mm²269 A210 A7.72 V (1.93%)392.3 V12.74 V (3.18%)3343.7 W✓ OK (≤3%)
150 mm²309 A241 A6.18 V (1.54%)393.8 V10.19 V (2.55%)2675.0 W✓ OK (≤3%)
185 mm²353 A275 A5.01 V (1.25%)395.0 V8.26 V (2.07%)2168.9 W✓ OK (≤3%)
240 mm²415 A324 A3.86 V (0.97%)396.1 V6.37 V (1.59%)1671.9 W✓ OK (≤3%)
300 mm²477 A372 A3.09 V (0.77%)396.9 V5.1 V (1.27%)1337.5 W✓ OK (≤3%)
400 mm²570 A445 A2.32 V (0.58%)397.7 V3.82 V (0.96%)1003.1 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 250 Ampere ved 100 Meter (400V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 250A over 100 meter (400V)?

Etter NEK 400 anbefales 120 mm² kobberkabel for 250A ved 100 meter (400V), som gir et spenningsfall på 7.72V (1.93%).

Hvor mange kW tåler 250A ved 400V?

Kursen leverer opptil 173.21 kW med 250A vern.