Kabeltverrsnitt for 250 Ampere ved 100 Meter (400V — NEK 400)
Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 250 A over 100 m ved 400V.
Copper Cable (≤3% Drop)120 mm²Drop: 7.72V (1.93%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 8.26V (2.07%)
Voltage at Load392.3 VLine Loss: 3343.7 W
Max Power & Breaker173.21 kW250A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 100m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 617.76 V (154.44%) | 0.0 V | 1019.02 V (254.76%) | 267500.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 370.66 V (92.66%) | 29.3 V | 611.41 V (152.85%) | 160500.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 231.66 V (57.92%) | 168.3 V | 382.13 V (95.53%) | 100312.5 W | Drop High |
| 6 mm² | 41 A | 32 A | 154.44 V (38.61%) | 245.6 V | 254.76 V (63.69%) | 66875.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 92.66 V (23.17%) | 307.3 V | 152.85 V (38.21%) | 40125.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 57.92 V (14.48%) | 342.1 V | 95.53 V (23.88%) | 25078.1 W | Drop High |
| 25 mm² | 101 A | 78 A | 37.07 V (9.27%) | 362.9 V | 61.14 V (15.29%) | 16050.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 26.48 V (6.62%) | 373.5 V | 43.67 V (10.92%) | 11464.3 W | Drop High |
| 50 mm² | 151 A | 118 A | 18.53 V (4.63%) | 381.5 V | 30.57 V (7.64%) | 8025.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 13.24 V (3.31%) | 386.8 V | 21.84 V (5.46%) | 5732.1 W | Drop High |
| 95 mm² | 232 A | 181 A | 9.75 V (2.44%) | 390.2 V | 16.09 V (4.02%) | 4223.7 W | Drop High |
| 120 mm² | 269 A | 210 A | 7.72 V (1.93%) | 392.3 V | 12.74 V (3.18%) | 3343.7 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 6.18 V (1.54%) | 393.8 V | 10.19 V (2.55%) | 2675.0 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 5.01 V (1.25%) | 395.0 V | 8.26 V (2.07%) | 2168.9 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 3.86 V (0.97%) | 396.1 V | 6.37 V (1.59%) | 1671.9 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 3.09 V (0.77%) | 396.9 V | 5.1 V (1.27%) | 1337.5 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 2.32 V (0.58%) | 397.7 V | 3.82 V (0.96%) | 1003.1 W | ✓ OK (≤3%) |
FAQ — Kabeltverrsnitt for 250 Ampere ved 100 Meter (400V — NEK 400)
Hvilket kabeltverrsnitt må jeg bruke for 250A over 100 meter (400V)?
Etter NEK 400 anbefales 120 mm² kobberkabel for 250A ved 100 meter (400V), som gir et spenningsfall på 7.72V (1.93%).
Hvor mange kW tåler 250A ved 400V?
Kursen leverer opptil 173.21 kW med 250A vern.
Related Lengths & Currents (400V)
250A · 5m (400V)250A · 10m (400V)250A · 15m (400V)250A · 20m (400V)250A · 25m (400V)250A · 30m (400V)250A · 35m (400V)250A · 40m (400V)250A · 45m (400V)250A · 50m (400V)250A · 60m (400V)250A · 70m (400V)10A · 100m (400V)16A · 100m (400V)20A · 100m (400V)25A · 100m (400V)32A · 100m (400V)40A · 100m (400V)50A · 100m (400V)63A · 100m (400V)80A · 100m (400V)100A · 100m (400V)125A · 100m (400V)160A · 100m (400V)200A · 100m (400V)