⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltverrsnitt for 325 Ampere ved 60 Meter (230V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 325 A over 60 m ved 230V.

Copper Cable (≤3% Drop)185 mm²Drop: 4.51V (1.96%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 4.59V (2.0%)
Voltage at Load225.5 VLine Loss: 1466.2 W
Max Power & Breaker74.75 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A556.4 V (241.91%)0.0 V917.8 V (399.04%)180830.0 WDrop High
2.5 mm²24 A18 A333.84 V (145.15%)0.0 V550.68 V (239.43%)108498.0 WDrop High
4 mm²32 A25 A208.65 V (90.72%)21.3 V344.17 V (149.64%)67811.2 WDrop High
6 mm²41 A32 A139.1 V (60.48%)90.9 V229.45 V (99.76%)45207.5 WDrop High
10 mm²57 A44 A83.46 V (36.29%)146.5 V137.67 V (59.86%)27124.5 WDrop High
16 mm²76 A59 A52.16 V (22.68%)177.8 V86.04 V (37.41%)16952.8 WDrop High
25 mm²101 A78 A33.38 V (14.51%)196.6 V55.07 V (23.94%)10849.8 WDrop High
35 mm²125 A97 A23.85 V (10.37%)206.2 V39.33 V (17.1%)7749.9 WDrop High
50 mm²151 A118 A16.69 V (7.26%)213.3 V27.53 V (11.97%)5424.9 WDrop High
70 mm²192 A150 A11.92 V (5.18%)218.1 V19.67 V (8.55%)3874.9 WDrop High
95 mm²232 A181 A8.79 V (3.82%)221.2 V14.49 V (6.3%)2855.2 WDrop High
120 mm²269 A210 A6.96 V (3.02%)223.0 V11.47 V (4.99%)2260.4 WDrop High
150 mm²309 A241 A5.56 V (2.42%)224.4 V9.18 V (3.99%)1808.3 WDrop High
185 mm²353 A275 A4.51 V (1.96%)225.5 V7.44 V (3.24%)1466.2 W✓ OK (≤3%)
240 mm²415 A324 A3.48 V (1.51%)226.5 V5.74 V (2.49%)1130.2 W✓ OK (≤3%)
300 mm²477 A372 A2.78 V (1.21%)227.2 V4.59 V (2.0%)904.1 W✓ OK (≤3%)
400 mm²570 A445 A2.09 V (0.91%)227.9 V3.44 V (1.5%)678.1 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 325 Ampere ved 60 Meter (230V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 325A over 60 meter (230V)?

Etter NEK 400 anbefales 185 mm² kobberkabel for 325A ved 60 meter (230V), som gir et spenningsfall på 4.51V (1.96%).

Hvor mange kW tåler 325A ved 230V?

Kursen leverer opptil 74.75 kW med 350A vern.