⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltverrsnitt for 425 Ampere ved 600 Meter (400V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 425 A over 600 m ved 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 11.81V (2.96%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 38.98V (9.74%)
Voltage at Load388.2 VLine Loss: 8697.1 W
Max Power & Breaker294.45 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6301.2 V (1575.3%)0.0 V10394.04 V (2598.51%)4638450.0 WDrop High
2.5 mm²24 A18 A3780.72 V (945.18%)0.0 V6236.42 V (1559.11%)2783070.0 WDrop High
4 mm²32 A25 A2362.95 V (590.74%)0.0 V3897.76 V (974.44%)1739418.8 WDrop High
6 mm²41 A32 A1575.3 V (393.83%)0.0 V2598.51 V (649.63%)1159612.5 WDrop High
10 mm²57 A44 A945.18 V (236.3%)0.0 V1559.11 V (389.78%)695767.5 WDrop High
16 mm²76 A59 A590.74 V (147.68%)0.0 V974.44 V (243.61%)434854.7 WDrop High
25 mm²101 A78 A378.07 V (94.52%)21.9 V623.64 V (155.91%)278307.0 WDrop High
35 mm²125 A97 A270.05 V (67.51%)129.9 V445.46 V (111.36%)198790.7 WDrop High
50 mm²151 A118 A189.04 V (47.26%)211.0 V311.82 V (77.96%)139153.5 WDrop High
70 mm²192 A150 A135.03 V (33.76%)265.0 V222.73 V (55.68%)99395.4 WDrop High
95 mm²232 A181 A99.49 V (24.87%)300.5 V164.12 V (41.03%)73238.7 WDrop High
120 mm²269 A210 A78.77 V (19.69%)321.2 V129.93 V (32.48%)57980.6 WDrop High
150 mm²309 A241 A63.01 V (15.75%)337.0 V103.94 V (25.99%)46384.5 WDrop High
185 mm²353 A275 A51.09 V (12.77%)348.9 V84.28 V (21.07%)37609.1 WDrop High
240 mm²415 A324 A39.38 V (9.85%)360.6 V64.96 V (16.24%)28990.3 WDrop High
300 mm²477 A372 A31.51 V (7.88%)368.5 V51.97 V (12.99%)23192.2 WDrop High
400 mm²570 A445 A23.63 V (5.91%)376.4 V38.98 V (9.74%)17394.2 WDrop High

FAQ — Kabeltverrsnitt for 425 Ampere ved 600 Meter (400V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 425A over 600 meter (400V)?

Etter NEK 400 anbefales 2× 400 mm² kobberkabel for 425A ved 600 meter (400V), som gir et spenningsfall på 11.81V (2.96%).

Hvor mange kW tåler 425A ved 400V?

Kursen leverer opptil 294.45 kW med 450A vern.