⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltverrsnitt for 45 Ampere ved 200 Meter (400V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 45 A over 200 m ved 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 9.53V (2.38%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 11.01V (2.75%)
Voltage at Load390.5 VLine Loss: 742.9 W
Max Power & Breaker31.18 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A222.4 V (55.6%)177.6 V366.85 V (91.71%)17334.0 WDrop High
2.5 mm²24 A18 A133.44 V (33.36%)266.6 V220.11 V (55.03%)10400.4 WDrop High
4 mm²32 A25 A83.4 V (20.85%)316.6 V137.57 V (34.39%)6500.2 WDrop High
6 mm²41 A32 A55.6 V (13.9%)344.4 V91.71 V (22.93%)4333.5 WDrop High
10 mm²57 A44 A33.36 V (8.34%)366.6 V55.03 V (13.76%)2600.1 WDrop High
16 mm²76 A59 A20.85 V (5.21%)379.2 V34.39 V (8.6%)1625.1 WDrop High
25 mm²101 A78 A13.34 V (3.34%)386.7 V22.01 V (5.5%)1040.0 W~ ≤5%
35 mm²125 A97 A9.53 V (2.38%)390.5 V15.72 V (3.93%)742.9 W✓ OK (≤3%)
50 mm²151 A118 A6.67 V (1.67%)393.3 V11.01 V (2.75%)520.0 W✓ OK (≤3%)
70 mm²192 A150 A4.77 V (1.19%)395.2 V7.86 V (1.97%)371.4 W✓ OK (≤3%)
95 mm²232 A181 A3.51 V (0.88%)396.5 V5.79 V (1.45%)273.7 W✓ OK (≤3%)
120 mm²269 A210 A2.78 V (0.69%)397.2 V4.59 V (1.15%)216.7 W✓ OK (≤3%)
150 mm²309 A241 A2.22 V (0.56%)397.8 V3.67 V (0.92%)173.3 W✓ OK (≤3%)
185 mm²353 A275 A1.8 V (0.45%)398.2 V2.97 V (0.74%)140.5 W✓ OK (≤3%)
240 mm²415 A324 A1.39 V (0.35%)398.6 V2.29 V (0.57%)108.3 W✓ OK (≤3%)
300 mm²477 A372 A1.11 V (0.28%)398.9 V1.83 V (0.46%)86.7 W✓ OK (≤3%)
400 mm²570 A445 A0.83 V (0.21%)399.2 V1.38 V (0.34%)65.0 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 45 Ampere ved 200 Meter (400V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 45A over 200 meter (400V)?

Etter NEK 400 anbefales 35 mm² kobberkabel for 45A ved 200 meter (400V), som gir et spenningsfall på 9.53V (2.38%).

Hvor mange kW tåler 45A ved 400V?

Kursen leverer opptil 31.18 kW med 45A vern.