Kabeltverrsnitt for 475 Ampere ved 120 Meter (400V — NEK 400)
Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 475 A over 120 m ved 400V.
Copper Cable (≤3% Drop)300 mm²Drop: 7.04V (1.76%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 8.71V (2.18%)
Voltage at Load393.0 VLine Loss: 5794.1 W
Max Power & Breaker329.09 kW500A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 120m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 1408.5 V (352.13%) | 0.0 V | 2323.37 V (580.84%) | 1158810.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 845.1 V (211.28%) | 0.0 V | 1394.02 V (348.51%) | 695286.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 528.19 V (132.05%) | 0.0 V | 871.26 V (217.82%) | 434553.8 W | Drop High |
| 6 mm² | 41 A | 32 A | 352.13 V (88.03%) | 47.9 V | 580.84 V (145.21%) | 289702.5 W | Drop High |
| 10 mm² | 57 A | 44 A | 211.28 V (52.82%) | 188.7 V | 348.51 V (87.13%) | 173821.5 W | Drop High |
| 16 mm² | 76 A | 59 A | 132.05 V (33.01%) | 268.0 V | 217.82 V (54.45%) | 108638.4 W | Drop High |
| 25 mm² | 101 A | 78 A | 84.51 V (21.13%) | 315.5 V | 139.4 V (34.85%) | 69528.6 W | Drop High |
| 35 mm² | 125 A | 97 A | 60.36 V (15.09%) | 339.6 V | 99.57 V (24.89%) | 49663.3 W | Drop High |
| 50 mm² | 151 A | 118 A | 42.26 V (10.56%) | 357.7 V | 69.7 V (17.43%) | 34764.3 W | Drop High |
| 70 mm² | 192 A | 150 A | 30.18 V (7.55%) | 369.8 V | 49.79 V (12.45%) | 24831.6 W | Drop High |
| 95 mm² | 232 A | 181 A | 22.24 V (5.56%) | 377.8 V | 36.68 V (9.17%) | 18297.0 W | Drop High |
| 120 mm² | 269 A | 210 A | 17.61 V (4.4%) | 382.4 V | 29.04 V (7.26%) | 14485.1 W | Drop High |
| 150 mm² | 309 A | 241 A | 14.09 V (3.52%) | 385.9 V | 23.23 V (5.81%) | 11588.1 W | Drop High |
| 185 mm² | 353 A | 275 A | 11.42 V (2.86%) | 388.6 V | 18.84 V (4.71%) | 9395.8 W | Drop High |
| 240 mm² | 415 A | 324 A | 8.8 V (2.2%) | 391.2 V | 14.52 V (3.63%) | 7242.6 W | Drop High |
| 300 mm² | 477 A | 372 A | 7.04 V (1.76%) | 393.0 V | 11.62 V (2.9%) | 5794.1 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 5.28 V (1.32%) | 394.7 V | 8.71 V (2.18%) | 4345.5 W | ✓ OK (≤3%) |
FAQ — Kabeltverrsnitt for 475 Ampere ved 120 Meter (400V — NEK 400)
Hvilket kabeltverrsnitt må jeg bruke for 475A over 120 meter (400V)?
Etter NEK 400 anbefales 300 mm² kobberkabel for 475A ved 120 meter (400V), som gir et spenningsfall på 7.04V (1.76%).
Hvor mange kW tåler 475A ved 400V?
Kursen leverer opptil 329.09 kW med 500A vern.
Related Lengths & Currents (400V)
475A · 5m (400V)475A · 10m (400V)475A · 15m (400V)475A · 20m (400V)475A · 25m (400V)475A · 30m (400V)475A · 35m (400V)475A · 40m (400V)475A · 45m (400V)475A · 50m (400V)475A · 60m (400V)475A · 70m (400V)10A · 120m (400V)16A · 120m (400V)20A · 120m (400V)25A · 120m (400V)32A · 120m (400V)40A · 120m (400V)50A · 120m (400V)63A · 120m (400V)80A · 120m (400V)100A · 120m (400V)125A · 120m (400V)160A · 120m (400V)200A · 120m (400V)