Kabeltverrsnitt for 475 Ampere ved 350 Meter (400V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 475 A over 350 m ved 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 7.71V (1.93%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 25.41V (6.35%)
Voltage at Load392.3 VLine Loss: 6337.2 W
Max Power & Breaker329.09 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4108.14 V (1027.03%)0.0 V6776.5 V (1694.13%)3379862.5 WDrop High
2.5 mm²24 A18 A2464.88 V (616.22%)0.0 V4065.9 V (1016.48%)2027917.5 WDrop High
4 mm²32 A25 A1540.55 V (385.14%)0.0 V2541.19 V (635.3%)1267448.4 WDrop High
6 mm²41 A32 A1027.03 V (256.76%)0.0 V1694.13 V (423.53%)844965.6 WDrop High
10 mm²57 A44 A616.22 V (154.06%)0.0 V1016.48 V (254.12%)506979.4 WDrop High
16 mm²76 A59 A385.14 V (96.28%)14.9 V635.3 V (158.82%)316862.1 WDrop High
25 mm²101 A78 A246.49 V (61.62%)153.5 V406.59 V (101.65%)202791.7 WDrop High
35 mm²125 A97 A176.06 V (44.02%)223.9 V290.42 V (72.61%)144851.2 WDrop High
50 mm²151 A118 A123.24 V (30.81%)276.8 V203.3 V (50.82%)101395.9 WDrop High
70 mm²192 A150 A88.03 V (22.01%)312.0 V145.21 V (36.3%)72425.6 WDrop High
95 mm²232 A181 A64.87 V (16.22%)335.1 V107.0 V (26.75%)53366.2 WDrop High
120 mm²269 A210 A51.35 V (12.84%)348.6 V84.71 V (21.18%)42248.3 WDrop High
150 mm²309 A241 A41.08 V (10.27%)358.9 V67.77 V (16.94%)33798.6 WDrop High
185 mm²353 A275 A33.31 V (8.33%)366.7 V54.94 V (13.74%)27404.3 WDrop High
240 mm²415 A324 A25.68 V (6.42%)374.3 V42.35 V (10.59%)21124.1 WDrop High
300 mm²477 A372 A20.54 V (5.14%)379.5 V33.88 V (8.47%)16899.3 WDrop High
400 mm²570 A445 A15.41 V (3.85%)384.6 V25.41 V (6.35%)12674.5 W~ ≤5%

FAQ — Kabeltverrsnitt for 475 Ampere ved 350 Meter (400V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 475A over 350 meter (400V)?

Etter NEK 400 anbefales 2× 400 mm² kobberkabel for 475A ved 350 meter (400V), som gir et spenningsfall på 7.71V (1.93%).

Hvor mange kW tåler 475A ved 400V?

Kursen leverer opptil 329.09 kW med 500A vern.